background image

16

5 Connecting to power supply

VEGASWING 61 • - transistor (NPN/PNP)

29225-EN-161125

5  Connecting to power supply

5.1  Preparing the connection

Always keep in mind the following safety instructions:

Warning:

Connect only in the complete absence of line voltage.

• 

The electrical connection must only be carried out by trained 

personnel authorised by the plant operator.

• 

Always switch off power supply, before connecting or disconnect-

ing the instrument.

In hazardous areas you must take note of the respective regulations, 

conformity and type approval certificates of the sensors and power 

supply units.

Connect the voltage supply according to the following diagrams. 

Take note of the general installation regulations. As a rule, connect 

VEGASWING 61 to vessel ground (PA), or in case of plastic vessels, 

to the next ground potential. On the side of the instrument housing 

there is a ground terminal between the cable entries. This connection 

serves to drain off electrostatic charges. In Ex applications, the instal-

lation regulations for hazardous areas must be given priority.
The data for power supply are specified in chapter "

Technical data

".

The instrument is connected with standard two-wire cable without 

screen. If electromagnetic interference is expected which is above the 

test values of EN 61326 for industrial areas, screened cable should 

be used.
Use cable with round cross-section. A cable outer diameter of 

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland. 

If you are using cable with a different diameter or cross-section, 

exchange the seal or use a suitable cable gland.
In hazardous areas, use only approved cable connections for 

VEGASWING 61.

Take note of the corresponding installation regulations for Ex applica-

tions.
Cover all housing openings conforming to standard according to 

EN 60079-1.

5.2  Connection procedure

With Ex instruments, the housing cover may only be opened if there is 

no explosive atmosphere present.
Proceed as follows:
1.  Unscrew the housing lid
2.  Loosen compression nut of the cable gland and remove blind 

plug

Note safety instructions

Take note of safety 

instructions for Ex 

applications

Voltage supply

Connection cable

Connection cable 

for Ex applications

Summary of Contents for VEGASWING 61

Page 1: ...Operating Instructions Vibrating level switch for liquids VEGASWING 61 transistor NPN PNP Document ID 29225...

Page 2: ...Adjustment 8 3 4 Storage and transport 9 3 5 Accessories 9 4 Mounting 4 1 General instructions 11 4 2 Mounting instructions 14 5 Connecting to power supply 5 1 Preparing the connection 16 5 2 Connecti...

Page 3: ...Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications These instructions are attached as documents to each instrument with Ex approval and are part of t...

Page 4: ...This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can result Warning If this warning is ignored injury to persons and or serious damage to...

Page 5: ...opriate or incorrect use of the instrument can give rise to application specific hazards e g vessel overfill or damage to system components through incorrect mounting or adjustment 2 4 General safety...

Page 6: ...ther information in the Safety Manual VEGASWING series 60 2 8 Safety instructions for Ex areas Please note the Ex specific safety information for installation and op eration in Ex areas These safety i...

Page 7: ...the components Housing lid Housing with electronics Process fitting with tuning fork 1 2 3 Fig 1 VEGASWING 61 1 Housing lid 2 Housing with electronics 3 Process fitting The type label contains the mo...

Page 8: ...condition i e the output is open safe state The tuning fork is piezoelectrically energised and vibrates at its mechanical resonance frequency of approx 1200 Hz The piezos are fixed mechanically and ar...

Page 9: ...ion the packages must be left closed and stored according to the orientation and storage markings on the outside Unless otherwise indicated the packages must be stored only under the following conditi...

Page 10: ...10 3 Product description VEGASWING 61 transistor NPN PNP 29225 EN 161125 The following plug connectors are available M12 x 1 ISO 4400 Harting HAN 7D Harting HAN 8D Amphenol Tuchel...

Page 11: ...int with vertical mounting The switching point applies to water in conjunction with the basic setting of the density switch 0 7 g cm 0 025 lbs in When mounting VEGASWING 61 make sure that this marking...

Page 12: ...k position with flange versions 1 Marking with flange version facing up Use the recommended cables see chapter Connecting to power supply and tighten the cable gland You can give your instrument addit...

Page 13: ...st be treated accordingly Bending the vibrating element will destroy the instrument Warning The housing must not be used to screw the instrument in Applying tightening force can damage internal parts...

Page 14: ...us products the surfaces of the tuning fork should be vertical in order to reduce buildup on the tuning fork On the screwed version you will find a marking on the hexagon With this you can check the p...

Page 15: ...leakage of the medium The service life of the gas tight leadthrough depends on the chemical resistance of the materials See Technical data Caution If it is determined e g via an error message from VEG...

Page 16: ...tal lation regulations for hazardous areas must be given priority The data for power supply are specified in chapter Technical data The instrument is connected with standard two wire cable without scr...

Page 17: ...he wires in the terminals by lightly pulling on them 9 Tighten the compression nut of the cable entry gland The seal ring must completely encircle the cable 10 Screw the housing lid back on The electr...

Page 18: ...ch for switching point adaptation 4 Ground terminal 5 Connection terminals We recommend connecting VEGASWING 61 in such a way that the switching circuit is open when there is a level signal line break...

Page 19: ...ig 11 PNP action 5 4 Wiring plan version IP 66 IP 68 1 bar 1 2 3 4 5 Fig 12 Wire assignment connection cable The numbers of the wires corre spond to the terminals of the instrument 1 brown voltage sup...

Page 20: ...ts Signal lamp 1 DIL switch for mode adjustment A B 2 DIL switch for sensitivity adjustment 3 Note Always immerse the tuning fork of VEGASWING 61 in a liquid to test its function Do not test the funct...

Page 21: ...n In products with a different density the switching point will shift in the direction of the housing or tuning fork end depending on the density and type of installation Note Keep in mind that foams...

Page 22: ...22 6 Setup VEGASWING 61 transistor NPN PNP 29225 EN 161125 Level Switching status Control lamp Fault any open flashes red...

Page 23: ...sed by the following e g Sensor Process Voltage supply Signal processing The first measure to take is to check the output signal In many cases the causes can be determined this way and the faults quic...

Page 24: ...ected Set the correct mode with the mode switch overflow protection dry run protection Wiring should be carried out according to the closed circuit principle Signal lamp flashes red Error on the vibra...

Page 25: ...bout the procedure in the download area of our homepage www vega com By doing this you help us carry out the repair quickly and without hav ing to call back for needed information If a repair is neces...

Page 26: ...an be recycled by spe cialised recycling companies We use recyclable materials and have designed the parts to be easily separable WEEE directive 2002 96 EG This instrument is not subject to the WEEE d...

Page 27: ...mm 0 839 in 316L Alloy C22 2 4602 316L with ECTFE coating 316L with PFA coating Materials non wetted parts Plastic housing plastic PBT Polyester Aluminium die cast housing Aluminium die casting AlSi10...

Page 28: ...3852 A G G1 American pipe thread conical ASME B1 20 1 NPT 1 NPT Flanges DIN from DN 25 ASME from 1 hygienic fittings Slotted nut DN 40 PN 40 Clamp 1 DIN 32676 ISO 2852 316L Clamp 2 DIN 32676 ISO 2852...

Page 29: ...Product density 1 g cm 0 036 lbs in water Product viscosity 1 mPa s Superimposed pressure 0 kPa Sensor installation Vertically from top Density selection switch 0 7 g cm Measuring accuracy Deviation 1...

Page 30: ...g cm 0 018 lb in 4 Switch position 0 7 g cm 0 025 lb in 5 Switching point at reference conditions notch 6 Tuning fork Influence of the process pressure to the switching point 1 2 3 4 12 174 1 38 551 1...

Page 31: ...ured up to an operating pressure of 100 bar 10000 kPa 1450 psig at a maximum process temperature of 50 C 122 F only with threaded versions Process temperature thread or flange temperature VEGASWING 61...

Page 32: ...C 392 F 250 C 482 F 20 290 1 14 5 40 580 64 928 Fig 29 Process temperature Process pressure with switch position 0 5 g cm sensitivity switch 1 Process pressure in bar psig 2 Process temperature in C...

Page 33: ...x 1 5 or 1 x closing cap NPT 1 x blind plug NPT Connection cable Wire cross section 0 5 mm AWG 20 Wire resistance 0 036 m 0 011 ft Tensile strength 1200 N 270 lbf Standard length 5 m 16 4 ft Max lengt...

Page 34: ...with approvals can have different technical specifications depending on the version For that reason the associated approval documents of these instruments have to be carefully noted They are part of t...

Page 35: ...rotection rating IP 66 IP 68 1 bar 1 Stainless steel housing precision casting 2 Aluminium housing VEGASWING 61 G A NPT G1A 1 NPT 18 5 mm 0 73 32 G A NPT 41 G1A 1 NPT 57 mm 2 24 50 mm 1 97 33 7 mm 1 3...

Page 36: ...36 9 Supplement VEGASWING 61 transistor NPN PNP 29225 EN 161125 VEGASWING 61 options 34 mm 1 34 178 mm 7 01 1 2 Fig 33 Options 1 Gas tight leadthrough 2 Temperature adapter...

Page 37: ...nen unter www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas...

Page 38: ...38 Notes VEGASWING 61 transistor NPN PNP 29225 EN 161125...

Page 39: ...39 Notes VEGASWING 61 transistor NPN PNP 29225 EN 161125...

Page 40: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Reviews: