13 Diagnostics and servicing
VEGAPULS Air 41 • Autarkic device with measured value transmission via radio technology
64808-EN-210426
Code
Text message
Cause
Rectification
S601
Overfilling
Danger of vessel overfilling
Make sure that there is no further filling
Check level in the vessel
S603
Impermissible operating
voltage
Lithium cell voltage too low
Check the voltage of the lithium cell
Code
Text message
Cause
Rectification
M500
Error in the delivery
status
The data could not be restored during the
reset to delivery status
Repeat reset
Load XML file with sensor data into the
sensor
M501
Error in the delivery
status
Hardware error EEPROM
Send instrument for repair
M507
Error in the instrument
settings
Error during setup
Error when carrying out a reset
False signal suppression faulty
Carry out reset and repeat setup
M508
No executable Bluetooth
software
Checksum error in Bluetooth software
Carry out software update
M509
Software update running
Software update running
Wait until software update is finished
13.4 Treatment of measurement errors
The tables below give typical examples of application-related meas-
urement errors.
The images in column "
Error description
" show the actual level as a
dashed line and the output level as a solid line.
1
2
Level
time
0
1 Real level
2 Level displayed by the sensor
Maintenance