15
5 Set up with the display and adjustment module PLICSCOM
VEGAPULS 68 • 4 … 20 mA/HART - four-wire
51905-EN-180222
from the sensor to the product surface. All false signals in this
area are detected by the sensor and saved after confirming with
[OK]
.
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
signal. The level would then no longer be detectable in this area.
5.3 Menu schematic
Information:
Depending on the version and application, the light-coloured menu
windows are not always available or offer nor selection possibility.
Basic adjustment
▶
Basic adjustment
1
Display
Diagnostics
Service
Info
Min. adjustment
1.1
0.00 %
=
30.000 m(d)
0.665 m(d)
Max. adjustment
1.2
100.00 %
=
0.000 m(d)
0.665 m(d)
Medium
1.3
Bulk solid
▼
not known
▼
Vessel form
1.4
not known
▼
Damping
1.5
0 s
Linearisation curve
1.6
Linear
Sensor-TAG
1.7
Sensor
Display
Basic adjustment
2
▶
Display
Diagnostics
Service
Info
Displayed value
2.1
Scaled
Display unit
2.2
Volume
▼
l
▼
Scaling
2.3
0 % = 0.0 l
100 % = 100.0 l
Backlight
2.4
Switched off
▼