5 Set up with the display and adjustment module PLICSCOM
VEGAPULS 68 • 4 … 20 mA/HART - four-wire
51905-EN-180222
5.2 Setup steps
1. Go to the menu "
Basic adjustment
" via the display and adjust-
ment module.
▶
Basic adjustment
Display
Diagnostics
Service
Info
2. Carry out the adjustment in the menu items "
Min. adjustment
" and
"
Max. adjustment
".
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3. Select in the menu item "
Medium
" the medium of your applica-
tion, for example "
Powder/Dust
".
Medium
Bulk solid
4. Select in the menu item "
Application
" the vessel and the vessel
form, for example, "
Silo
".
Vessel form
Silo
Since the radar sensor is a distance measuring instrument, it is the
distance from the sensor to the product surface that is measured. To
indicate the actual level, the measured distance must be assigned to
a certain height percentage.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
Set parameters
Setup - Adjustment