6 Supplement
6.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions are valid for approved instruments (e.g. with
Ex approval). These data can differ from the data listed herein, for example regarding the process
conditions or the voltage supply.
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar
Cable entry/plug
1)
Ʋ Single chamber housing
–
1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5
or:
–
1 x closing cap M20 x 1.5; 1 x blind plug M20 x 1.5
or:
–
1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
–
1␣x plug (depending on the version), 1␣x blind stopper
M20␣x␣1.5
Ʋ Double chamber housing
–
1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm), 1 x
blind plug M20 x 1.5; 1 x blind plug M16 x 1.5 or
optionally available with 1 x plug M12 x 1 for external
display and adjustment unit
or:
–
1 x closing cap ½ NPT, 1 x blind plug ½ NPT, 1 x blind
plug M16 x 1.5 or optionally 1 x plug M12 x 1 for exter
-
nal display and adjustment unit
or:
–
1 x plug (depending on the version), 1 x blind plug
M20 x 1.5; 1 x blind plug M16 x 1.5 or optionally avail
-
able with 1 x plug M12 x 1 for external display and
adjustment unit
Spring-loaded terminals for wire cross-
section
< 2.5 mm² (AWG 14)
Voltage supply
Operating voltage
Ʋ Non-Ex instrument
9 … 32 V DC
Ʋ Ex ia instrument
9 … 24 V DC
Ʋ Ex-d instrument
16 … 32 V DC
Operating voltage with illuminated display and adjustment module
Ʋ Non-Ex instrument
12 … 32 V DC
Ʋ Ex ia instrument
12 … 24 V DC
Ʋ Ex-d instrument
20 … 32 V DC
Power supply by
DP/PA segment coupler
1)
Depending on the version M12 x 1, according to DIN 43650, Harting, 7/8" FF.