5 Set up with the display and adjustment module PLICSCOM
VEGAPULS 67 • Profibus PA
51902-EN-160620
2. Select the menu item "
Service
" with
[->]
and confirm with
[OK]
.
Now the menu item "
False signal suppression
" is displayed.
3. Confirm "
False signal suppression - Change now
" with
[OK]
and
select in the below menu "
Create new
". Enter the actual distance
from the sensor to the product surface. All false signals in this
area are detected by the sensor and saved after confirming with
[OK]
.
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
signal. The level would then no longer be detectable in this area.
5.3 Menu schematic
Information:
Depending on the version and application, the highlighted menu
windows may not always be available.
Basic adjustment
▶
Basic adjustment
1
Display
Diagnostics
Service
Info
Sensor address
1.1
000
Min. adjustment
1.2
000.0 %
=
10.000 m(d)
1.245 m(d)
Max. adjustment
1.3
100.0 %
=
0.000 m(d)
6.789 m(d)
Medium
1.4
Bulk solid
Vessel form
1.5
Silo
Linearisation curve
1.6
Linear
Channel
1.7
PV lin. value
Damping
1.8
1 s
Sensor-TAG
1.9
Sensor