
5
.
6
W
iring plan
-
version
IP
66
/
IP
68
,
1
bar
1
2
F
ig
.
10
:
W
ire assignment
fi
x
-
connected connection cable
1
brown
(
+
)
and blue
(-)
to power supply or to the processing system
2
S
hielding
5
.
7
S
witch
-
on phase
A
fter
VEGAPULS
62
is connected to the bus system
,
the instrument
carries out a self
-
test for approx
.
30
seconds
.
T
he following steps are
carried out
:
l
I
nternal check of the electronics
l
I
ndication of the instrument type
,
hardware and software version
,
measurement loop name on the display or
PC
l
I
ndication of the status message
"
F
105
D
etermine measured
value
"
on the display or
PC
l
S
tatus byte goes brie
fl
y to fault value
A
s soon as a plausible measured value is found
,
it is outputted to the
signal cable
.
T
he value corresponds to the actual level as well as the
settings already carried out
,
e
.
g
.
factory setting
.
W
ire assignment con
-
nection cable
VEGAPULS
62
standpipe version
•
F
oundation
F
ieldbus
19
5
C
onnecting to the bus system
36510
-
EN
-
120301