E
030
l
S
ensor in boot phase
l
value not valid
à
C
heck sensor parameter adjustment
?
E
034
l
EEPROM CRC
error
à
S
witch the instrument o
ff
and on
à
C
arry out a reset
à
S
end instrument for repair
?
E
035
l
ROM CRC
error
à
S
witch the instrument o
ff
and on
à
C
arry out a reset
à
S
end instrument for repair
?
E
036
l
I
nstrument software not executable
(
during software update or
after failed update
)
à
W
ait until software update is
fi
nished
à
C
arry out another software update
?
E
053
l
S
ensor measuring range not read correctly
à
C
ommunication error
:
C
heck sensor cable and screening
?
E
062
l
P
ulse priority too small
à
I
ncrease under
"
O
utput
"
the entry
"
P
ulse output all
"
so that
max
.
one pulse per second is outputted
.
?
E
110
l
R
elay switching points too close together
à
I
ncrease the di
ff
erence between the two relay switching points
?
E
111
l
R
elay switching points interchanged
à
C
hange relay switching points for
"
O
n
/
O
ff
"
VEGAMET
625
•
D
ouble channel
HART
signal conditioning instrument
55
9
M
aintenance and fault recti
fi
cation
28970
-
EN
-
110801