S
tatus
code
D
escription according to
P
ro
-
fi
bus standard
P
ossible cause
0
x
0
C
bad
-
sensor failure
l
H
ardware error
l
C
onverter error
l
L
eakage pulse error
l
T
rigger error
0
x
10
bad
-
sensor failure
l
M
easured value generation error
0
x
1
f
bad
-
out of service constant
"
O
ut of
S
ervice
"
mode switched on
0
x
44
uncertain
-
last unstable value
F
ailsafe replacement value
(
F
ailsafe
-
M
ode
= "
L
ast value
"
and
already valid measured value since switching on
)
0
x
48
uncertain substitute set
l
S
witch on simulation
l
F
ailsafe replacement value
(
F
ailsafe
-
M
ode
= "
F
safe value
"
)
0
x
4
c
uncertain
-
initial value
F
ailsafe replacement value
(
F
ailsafe
-
M
ode
= "
L
ast valid value
"
and
no valid measured value since switching on
)
0
x
51
uncertain
-
sensor
;
conversion
not accurate
-
low limited
S
ensor value
<
lower limit
0
x
52
uncertain
-
sensor
;
conversion
not accurate
-
high limited
S
ensor value
>
upper limit
0
x
80
good
(
non
-
cascade
) -
OK
OK
0
x
84
good
(
non
-
cascade
) -
active
block alarm
S
tatic revision
(
FB
,
TB
)
changed
(
10
sec
.
active
,
after the parameter
of the static category was written
)
0
x
89
good
(
non
-
cascade
) -
active ad
-
visory alarm
-
low limited
L
o
-
A
larm
0
x
8
a
good
(
non
-
cascade
) -
active ad
-
visory alarm
-
high limited
H
i
-
A
larm
0
x
8
d
good
(
non
-
cascade
) -
active cri
-
tical alarm
-
low limited
L
o
-
L
o
-
A
larm
0
x
8
e
good
(
non
-
cascade
) -
active cri
-
tical alarm
-
high limited
H
i
-
H
i
-
A
larm
58
VEGAFLEX
61
•
P
ro
fi
bus
PA
10
S
upplement
31835
-
EN
-
100426