51
10 Supplement
VEGACAL 62 • Profibus PA
30025-EN-160331
Housing material
Version
IP-protection class
NEMA protection
Plastic
Single chamber
IP 66/IP 67
NEMA 4X
Double chamber
IP 66/IP 67
NEMA 4X
Aluminium
Single chamber
IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)
NEMA 6P
NEMA 6P
Double chamber
IP 66/IP 67
IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)
NEMA 4X
NEMA 6P
NEMA 6P
Stainless steel, electro-
polished
Single chamber
IP 66/IP 68 (0.2 bar)
NEMA 6P
Stainless steel, precision
casting
Single chamber
IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)
NEMA 6P
NEMA 6P
Double chamber
IP 66/IP 67
IP 66/IP 68 (0.2 bar)
IP 68 (1 bar)
NEMA 4X
NEMA 6P
NEMA 6P
Overvoltage category
The feeding power supply unit can be connected to
networks of overvoltage category III.
Protection class
II (IEC 61010-1)
Approvals
Instruments with approvals can have different technical specifications depending on the version.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded under www.vega.com, "
VEGA Tools
"
and "
Instrument search
" as well as in the general download area.
10.2 Profibus PA
Instrument master file
The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.
These data are, e.g. the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-
cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-
ment in the configuration tool.
Ident number
Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user
organisation (PNO). This ID number is also included in the name of the GSD file. For VEGACAL 62
the ID number is
0x076E(hex)
and the GSD file
CL__076E.GSD
. Optionally to this manufacturer-
specific GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGACAL 62
you have to use the general GSD file
PA139700.GSD
. If the general GSD file is used, the sensor
must be set to the profile-specific ident number via the DTM software. By default, the sensor oper-
ates with the manufacturer-specific ID number.