14
4 Mounting
VEGACAL 62 • Profibus PA
30025-EN-160331
Prior to setup you have to replace these protective caps with ap-
proved cable glands or close the openings with suitable blind plugs.
4.2 Mounting instructions
During operation, the probe must not touch any installations or the
vessel wall. The measured value can also change if the distance to
the vessel wall changes considerably. If necessary, secure the end of
the probe (insulated).
1
2
1
2
Fig. 5: Fasten the probe
1 Measuring probe
2 Plastic socket
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the vessel bottom.
If the instrument is mounted in the filling stream, unwanted false
measurement signals can be generated. For this reason, mount the
instrument at a position in the vessel where no disturbances, e.g. from
filling openings, agitators, etc., can occur.
This applies particularly to instrument versions with a longer probe.
Installation position
Inflowing medium