9
1 Functional safety
VEGACAL series 60 • Two-wire 4 … 20 mA/HART
35593-EN-181129
The calculations are also based on the specifications stated in chap-
ter "
Planning
".
After 8 to 12 years, the failure rates of the electronic components will
increase, whereby the derived PFD and PFH values will deteriorate
(IEC 61508-2, 7.4.7.4, note 3).
Applies to overfill and dry run protection:
λ
sd
0 FIT
λ
su
212 FIT
λ
dd
458 FIT
λ
du
208 FIT
DC
S
0 %
DC
D
68 %
MTBF = MTTF + MTTR
0.93 x 10
6
h
E013 (no measured value available)
< 10 sek.
E036/E037 (no executable sensor software)
< 1 h
Single channel architecture
SIL
SIL2
HFT
0
Instrument type
Type B
Applies to overfill and dry run protection:
SFF
76 %
PFD
avg
T
Proof
= 1 year
T
Proof
= 5 years
< 0.091 x 10
-2
< 0.182 x 10
-2
PFH
< 0.208 x 10
-6
/h
The chronological sequence of PFD
avg
is nearly linear to the operating
time over a period up to 10 years. The above values apply only to the
T
Proof
interval after which a recurring function test must be carried out.
Service life
Failure rates
Fault reaction time
Specific characteristics
Time-dependent process
of PFD
avg
Summary of Contents for VEGACAL 60 Series
Page 1: ...Safety Manual VEGACAL series 60 Two wire 4 20 mA HART Document ID 35593...
Page 11: ...11 2 Supplement VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129 2 Supplement...
Page 12: ...12 2 Supplement VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...
Page 13: ...13 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...
Page 14: ...14 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...
Page 15: ...15 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...