background image

9

1 Functional safety

VEGACAL series 60 • Two-wire 4 … 20 mA/HART

35593-EN-181129

The calculations are also based on the specifications stated in chap-

ter "

Planning

".

After 8 to 12 years, the failure rates of the electronic components will 

increase, whereby the derived PFD and PFH values will deteriorate 

(IEC 61508-2, 7.4.7.4, note 3).

Applies to overfill and dry run protection:

λ

sd

0 FIT

λ

su

212 FIT

λ

dd

458 FIT

λ

du

208 FIT

DC

S

0 %

DC

D

68 %

MTBF = MTTF + MTTR

0.93 x 10

6

 h

E013 (no measured value available)

< 10 sek.

E036/E037 (no executable sensor software)

< 1 h

Single channel architecture

SIL

SIL2

HFT

0

Instrument type

Type B

Applies to overfill and dry run protection:

SFF

76 %

PFD

avg

T

Proof

 = 1 year

T

Proof

 = 5 years

< 0.091 x 10

-2

< 0.182 x 10

-2

PFH

< 0.208 x 10

-6

/h

The chronological sequence of PFD

avg

 is nearly linear to the operating 

time over a period up to 10 years. The above values apply only to the 

T

Proof

 interval after which a recurring function test must be carried out.

Service life

Failure rates

Fault reaction time

Specific characteristics

Time-dependent process 

of PFD

avg

Summary of Contents for VEGACAL 60 Series

Page 1: ...Safety Manual VEGACAL series 60 Two wire 4 20 mA HART Document ID 35593...

Page 2: ...1 Functional safety 3 1 1 General information 3 1 2 Planning 4 1 3 Instrument parameter adjustment 6 1 4 Setup 7 1 5 Reaction during operation and in case of failure 7 1 6 Recurring function test 8 1...

Page 3: ...ant architecture is excluded The SIL conformity is confirmed by the verification documents in the appendix SIL Safety Integrity Level HFT Hardware Fault Tolerance SFF Safe Failure Fraction PFDavg Aver...

Page 4: ...According to IEC 61511 1 paragraph 11 4 4 the failure tolerance HFT can be reduced by one for service proven subsystems if the fol lowing conditions are met The instrument is service proven Only proce...

Page 5: ...responding portions of the failure rates must be assigned to the dangerous failures The stated values in chapter Safety relevant characteristics can thus worsen The processing unit must correspond to...

Page 6: ...s e g HART I C Bus are not used for transmission of safety relevant information The measuring system should be used appropriately taking pressure temperature density dielectric value and chemical prop...

Page 7: ...rized modification the set parameters must be protected against unintentional access Activate the password protection in the adjustment software Activate the PIN on the display and adjustment module A...

Page 8: ...hitectures it is a good idea to verify the effect of the redundancy through recurring function tests at appropriate intervals Please carry out the test in such a way that the correct safety function i...

Page 9: ...F MTTF MTTR 0 93 x 106 h E013 no measured value available 10 sek E036 E037 no executable sensor software 1 h Single channel architecture SIL SIL2 HFT 0 Instrument type Type B Applies to overfill and d...

Page 10: ...years Multiple channel architecture If the measuring system is used in a multiple channel architecture the safety relevant characteristics of the selected structure of the meas chain must be calculat...

Page 11: ...11 2 Supplement VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129 2 Supplement...

Page 12: ...12 2 Supplement VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Page 13: ...13 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Page 14: ...14 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Page 15: ...15 Notes VEGACAL series 60 Two wire 4 20 mA HART 35593 EN 181129...

Page 16: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...

Reviews: