35
6 Set up with the display and adjustment module
VEGABAR 81 • 4
… 20 mA
45025-EN-140228
user especially when adjusting the switching point on the limit signal
transmitter.
In the menu items "
Current output
" you determine the properties of
the current output.
On instruments with a 2nd integrated current output, the properties for
each current output are adjusted individually. The following descrip
-
tions apply to both current outputs.
In the menu item "
Current output mode
" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4
… 20 mA, failure mode
< 3.6 mA.
In the menu item "
Current output Min./Max.
", you determine the reac
-
tion of the current output during operation.
The default setting is min. current 3.8
mA and max. current 20.5
mA.
In the menu item "
Lock/unlock adjustment
", you can protect the
sensor parameters against unauthorized modification. The PIN is
activated/deactivated permanently.
The following adjustment functions are possible without entering the
PIN:
•
Select menu items and show data
•
Read data from the sensor into the display and adjustment mod
-
ule.
Caution:
With active PIN, adjustment via PACTware/DTM as well as other
systems is also blocked.
You can change the PIN number under "
Additional adjustments -
PIN
".
This menu item enables the setting of the requested national lan
-
guage.
Setup - Current output
Setup - Current output 1
and 2 (mode)
Setup - Current output 1
and 2 (min./max.)
Lock/release setup - Ad-
justment
Display - Language