13 Supplement
VEGABAR 39 • Three-wire 1 x transistor or 4 … 20 mA
57536-EN-200831
Nominal measuring ranges and overload capacity in psi
Nominal range
Overload capacity, max. pressure Overload capacity, min. pressure
Gauge pressure
0 … +5 psig
+60 psig
-14.5 psig
0 … +15 psig
+60 psig
-14.5 psig
0 … +30 psig
+145 psig
-14.5 psig
0 … +75 psig
+290 psig
-14.5 psig
0 … +150 psig
+580 psig
-14.5 psig
0 … +300 psig
+1740 psig
-14.5 psig
0 … +900 psig
+4350 psig
-14.5 psig
0 … +1450 psig
+4350 psig
-14.5 psig
0 … +3000 psig
+7250 psig
-14.5 psig
0 … +9000 psig
+17400 psig
-14.5 psig
0 … +15000 psig
+29000 psig
-14.5 psig
-3 … +3 psig
+60 psig
-14.5 psig
-7 … +7 psig
+60 psig
-14.5 psig
-14.5 … 0 psig
+60 psig
-14.5 psig
Absolute pressure
0 … +15 psi
+43 psi
0 psi
0 … +30 psi
+145 psi
0 psi
0 … +75 psi
+290 psi
0 psi
0 … +150 psi
+580 psi
0 psi
0 … +300 psi
+1740 psi
0 psi
Adjustment ranges
Specifications refer to the nominal measuring range, pressure values lower than -1 bar cannot be
set
Zero/Span adjustment:
Ʋ Zero
-20 … +95 %
Ʋ Span
-120 … +120 %
Maximum permissible Turn Down
Unlimited (recommended 20 : 1)
Switch-on phase
Start-up time with operating voltage U
B
≤ 2 s
Staring current for run-up time
≤ 3.6 mA
Output variable - three-wire 4 … 20 mA
Output signal
4 … 20 mA (active)
Connection technology
Three-wire
Range of the output signal
3.8 … 20.5 mA (default setting)
Signal resolution
5 µA