39
7 Set up with the integrated display and adjustment unit
VEGABAR 39 • Three-wire 1 x transistor or 4 … 20 mA
57536-EN-200831
•
HI
Information:
To reset the pointer function, the VEGA Tools app or PACTware/DTM
is required.
This menu item displays the hardware and software status as well as
the serial number of the device.
Menu item code:
•
INF
Parameter:
•
HW
•
SW
•
SN
In this menu item you simulate switching states of the transistor out-
puts or current values of the 4 … 20 mA output. This allows the signal
path to be tested, e.g. via downstream display instruments or the
input card of the control system. The simulation values are: Pressure,
current, switching status.
Note:
Make sure the connected downstream devices are activated during
the simulation.
Menu item code:
•
SIM
Parameter:
•
Numerical value for pressure or current
•
Open or closed for switching output
Note:
Without manual deactivation, the sensor terminates the simulation
automatically after 60 minutes.
Sensor information
Simulation