Initial Setup Of The Console Using Workflow Wizard
Setup>Tank>Profile
32
Setup>Tank>Profile
Charts define how the console calculates the volu
m
e of fuel in each tank. A point in a chart
specifies a height value at a certain volu
m
e of fuel (chart data is stored for each
m
onitored
tank). This infor
m
ation is critical for proper operation. This screen lets you
m
anually setup a
tank chart using one of four tank profiles listed below.
You
m
ust have entered the dia
m
eter and full volu
m
e before selecting a tank chart (see
“Setup>Tank>General”).
Select a tank fro
m
the icon list on the botto
m
of the screen to configure.
Tank Profile
Touch to select a tank profile option:
One Point
-This option uses only the 100% (full) volu
m
e to profile a tank.
This selection can be used for horizontally installed, flat-end cylindrical tanks, and when
AccuChart is available for this tank.
Four Point
- This option requires 4 points to profile the tank. The requested volu
m
es are at
percentages of height (e.g., the 75% volu
m
e of a 96" dia
m
eter tank equals the volu
m
e at a
height which is 75% of 96" or 72").
This selection can be used for all rounded- and dished-end tanks, and should be selected
when AccuChart is available for these type tanks.
Twenty Point
- This option uses 20 Points to profile a tank.
The requested volu
m
es are percentages of height (e.g., the
5% volu
m
e of a 96" dia
m
eter tank = the volu
m
e at a height
which is 5% of 96" or 4.8”).
This selection can be used for all rounded-end and dished-
end tanks.
Linear
- This option requires only the 100% (full) volu
m
e to
profile a tank.
NOTE:
Instead of entering a dia
m
eter value in the dia
m
eter
field, enter a height value in the dia
m
eter field of the
“Setup>Tank>General” screen.
This profile can be used for flat-end cylindrical tanks stand-
ing on end, and for rectangular tanks.
Multi Point
- This option is used for charts having
m
ore
than 20 points. See
Setup > Tank > Multi Point
for
m
ore infor-
m
ation.
Full Volume
[Read-only field] Total capacity and the dia
m
eter (full
height) of the tank.
This infor
m
ation can be handy when you are entering chart
infor
m
ation. The Full Volu
m
e value is entered in
End Shape
[Field only available when you select
One Point
for Tank Pro-
file field]
Enter a value fro
m
0 to 1.0 in 0.1 incre
m
ents (0.3 is the rec-
o
mm
ended value for dished-end tanks).