PLLD Grounding Clamp Installation Guide

P/N 577014-012

2

Kit Contents

Veeder-Root parts required to install the PLLD Transducer grounding clamp are listed in Table 1.

Installation Steps

 FAILURE TO FOLLOW THE STEPS BELOW MAY IMPAIR INTRINSIC SAFETY, CAUSE 
DAMAGE TO PROPERTY, ENVIRONMENT, RESULTING IN SERIOUS INJURY OR DEATH

1.

Before installing this device, turn Off, tag/lock out power to the system, including console and 
submersible pumps. 

2.

A separate 4mm

2

 (minimum) wire must be run from the site earth ground to the STP sump in a non-

intrinsically safe conduit or duct (see Figure 1). DO NOT CONNECT THE CLAMP OR BODY OF 
THE PLLD PRESSURE SENSOR TO ANY INTRINSCALLY SAFE WIRE THAT CONNECTS TO 
THE TLS CONSOLE.

3.

Using the ring terminal supplied in the kit, insert the stripped ground wire into the barrel of the ring 
terminal. 

4.

Use a properly sized crimping tool to ensure a good tight bond (see Figure 2). 

5.

Place the clamp around the sensor and attach the ring terminal to the clamp with the clamp bolt. 

6.

Securely tighten the clamp bolt until the clamp tightly grips the sensor body and no longer can be 
rotated by hand.

7.

Confirm continuity between the PLLD sensor body and ground at the electrical panel and between 
the electrical panel to the TLS console chassis (reference Figure 3).

Table 1. PLLD Grounding Kit (Part Number 330020-285)

Item

Qty.

Description

P/N

1

1

Clamp grounding

331285-002

2

1

Ring terminal - 1/4”, 12-10 AWG

576048-061

3

1

1/4”-20 x 1.00 “ bolt

514100-407

4

1

1/4”-20 nut hx sst w/lock washer

511000-251

5

1

PLLD Grounding Clamp Installation Guide

577014-012

OFF

Summary of Contents for PLLD

Page 1: ...barricades safety tape and your vehicle to block the work area READ ALL RELATED MANUALS Knowledge of all related procedures before you begin work is important Read and understand all manuals thoroughly If you do not understand a procedure ask someone who does WARNING This product is to be installed and operated in the highly combustible environment of a gasoline tank where flammable liquids and ex...

Page 2: ...TS TO THE TLS CONSOLE 3 Using the ring terminal supplied in the kit insert the stripped ground wire into the barrel of the ring terminal 4 Use a properly sized crimping tool to ensure a good tight bond see Figure 2 5 Place the clamp around the sensor and attach the ring terminal to the clamp with the clamp bolt 6 Securely tighten the clamp bolt until the clamp tightly grips the sensor body and no ...

Page 3: ...each tank sump 2 All sump earths are connected to common point 3 From the common point earth is connected to an Earth spike 4 From the common point earth is also connected to the building earth in the distribution panel Building electrical distribution panel 2 012 3 eps Securely crimp stripped barrier wire in ring terminal Slip ring terminal onto bolt and screw bolt into clamp nut Tighten bolt unt...

Page 4: ...1 2 3 4 5 6 PRESSURE LINE LEAK INTERFACE MODULE Conduit or ducting Attach cable shield to ground lug closest to conduit duct entry Intrinsically Safe Bay of Console AC Mains Breaker Panel Shield Ground wire with 4 mm cross sectional area minimum Connects to the site s earth ground 2 PLLD sensor grounding clamp Tighten bolt until clamp cannot be rotated by hand Non Intrinsically safe conduit or duc...

Reviews: