9
DIS-51 To TLS Console Wiring Connections
Connection Instructions - DIS-51 To TLS-350R
TLS2P Software Setup For DIS-51
Go to Menu>System Setup >Comm>Serial Port and select
Serial Port 2
. Then
select/enter the following parameters:
• Comm Type - SERIAL
• Handshaking - None
• Baud Rate - 9600
• Parity - NO PARITY
• Data Length - 8
• Stop Bits - 1
Connection Instructions - DIS-51 To TLS-350R
OPTION 1
This is the preferred option and requires a Single Port Kit P/N 461-100-4102
which includes:
• DIS-51 Interface Module for TLS-350R, provides single RS-485 Port, P/N
Figure 5. Single Port RS-485 Module For TLS-350R - DCD Configuration
• Flat Cable, P/N 222-007-0001
Summary of Contents for DIS-51
Page 1: ...Manual No 577014 445 Revision C DIS 51 Installation Setup Operation Guide ...
Page 10: ...6 Introduction Wiring Connections Figure 2 DIS 51 Junction Box Wiring Diagram ...
Page 11: ...7 Introduction Wiring Connections Figure 3 Serial Comm Wiring Input Options ...
Page 31: ...27 Operating Instructions Alarm screens This page intentionally left blank ...
Page 32: ......