X2-O
PERATIONS
M
ANUAL
B
UTTON
D
ISPLAY
Doc: 70-00-0950A, Serie X2, 20211220
© Vector Controls GmbH, Schweiz
Page 15-16
Subjects to alteration
www.vectorcontrols.com
V
ECTOR
5.6
Display total run time for digital outputs
Deactivated outputs are not displayed!
Procedure
1.
Press the ( /
) button longer than 2 seconds.
➔
SEL
and the actual
Date
and
Time
are displayed alternatingly.
2.
Press the ( ) or ( ) button until the digital output submenu
do
and
SEL
is displayed.
3.
Press the ( /
) button and select the desired output with
the ( ) ( ) button.
➔
do
, the output number and the value are displayed.
4.
Press the ( /
) button again
➔
do
, the output number and the total runtime of the output are
displayed.
If the runtime is greater than 9999 hours, one bar appears on the
side bar for every 10'000 hours.
The example on the right corresponds to 30345 hours runtime.
Maximum time is 65535 hours = 7.5 years.
5.
Press the ( ) or ( ) button to select the next output.
6.
Press the ( ) button to finish the inspection.
5.7
Display Software Version
Overview
This section describes how to display the software version of the installed X2 operating system and the firmware version
of the display / operation terminal.
Procedure
1.
Press the (
) and (
) button simultaneous longer than 2 seconds.
➔
BASE
and the software version of the X2 system and
OP
and the
firmware version of the display / operation terminal are displayed
alternatingly.
2.
Press the (
) button to go back to the start menu.