6.
Press the ( /
) button and assign one of the following functions
to the program with the ( ) ( ) button:
no
= Switching time not activated
OP
= Operating mode ON (Occupied), ECO (Unoccupied) or OFF
(protective operation)
LP
= Setpoint of a control loop (setting range 0-100%, °C/°F,
Pascal)
AO
= Positioning of the analog output (output must be in
manual mode!)
FAN
= Fan control (fan stages from FSP0-3 and Auto)
do
= Positioning of the digital output (output must be in
manual mode!)
Hday = Annual time schedule. (holidays)
➔
1 bar indicates setting step 1 is executed.
…
For setting a holiday "Hday" see
chapter 5.3.3
7.
Press the ( /
) button and adjust the time from 00:00…23:45
in
15 minutes steps with the ( ) ( ) button.
➔
2 bars indicate setting step 2 is executed.
8.
Press the ( /
) button to select Monday (Day 1).
9.
Press the ( ) button to execute the program on Monday (Day 1).
➔
A triangle symbol is displayed above the 1.
➔
3 top bar symbols are displayed.
10.
Press the ( ) button to
not
execute the program on Monday
(Day 1).
➔
The triangle symbol above the 1 disappears.
➔
The 3 top bar symbols disappear.
11.
Press the ( /
) button to go to the next day.
➔
DAY1
(Day 1) and
Pr01
(Program 1) is displayed in this
example.
➔
3 bars indicate setting step 3 is executed.
12.
Repeat this process to set
DAY2
to
DAY7
(Tuesday to Sunday).
➔
Triangle symbol indicate the days of the week the program will be
executed.
13.
Set the action to be performed by pressing the ( ) ( ) and
( /
) button depending on function selected in instruction No. 5:
a.
OP (operating mode):
ON
= Occupied, normal operation
ECO
= Unoccupied, reduced operation
OFF
= protective operation
b.
LP (control loop set point)
LP01
-
LP0x
*:
°C/°F
c.
AO (analogue output position)
Ao01
-
Ao0x
**:
0-100%
d.
FAN (fan control, fan speed)
FAN1
-
FAN2
:
fan speed 0-3 (FSP0-FSP3)
Auto mode (Auto)
e.
do (digital output position)
do01
-
do0x
***:
ON = enabled
OFF = disabled
➔
4 and 5 bars indicate setting step 4 rep. 5 is executed.
* The number of available control loops depends on the used X2-controller.
** The number of available analogue outputs depends on the used X2-
controller.
*** The number of available digital outputs depends on the used X2-
controller.
OP
➔