TLC3-FCR-M Engineering Manual

 

 

Doc: 70-00-0181, V3.0 Date: 20120424 

© Vector Controls GmbH, Switzerland 

Page 9 

Subject to alteration 

Configuration of outputs 

FC 18 

Configuration of analog output signal 
0

 

= 0-10V 

1

 

= 2-10V 

2

 

= Manual override (useful for commissioning) 

When low fan speed: 25% output 
When medium fan speed 50% output 
When high fan speed 100% output 

0-2 

0 (0-10V) 

Configuration of inputs (only for TLC3-FCR-M2) 

FC 19 

External input:  

0 = No external input 
1 = External temperature sensor 
2 = Occupation sensor – Comfort / Economy 
3 = Occupation sensor – Comfort / Off 
4 = Heat / Cool changeover  
5 = Key card with alternative setpoint 

0…8 

FC 20 

Activation delay (Minutes) = the time the binary input needs to be open 
before economy/off mode is activated. 

0…255 min 

FC 21 

Auto-changeover limit heating FC20 = 4 
or economy setpoint in heating mode if FC20 = 5 

-40…60°C (160°F) 

16°C (61°F) 

FC 22 

Auto-changeover limit cooling FC20 = 4 
or economy setpoint in cooling mode if FC20 = 5 

-40…60°C (160°F) 

28°C (82°F) 

 

Configuring the function of the external input 

 

FC19 = 0 

Input not used 

 

FC19 = 1 

External control input 

The external sensor is the control input. The internal sensor will 

be disabled.  

FC19 = 2 

Switching Economy and 

Comfort modes 

Economy (unoccupied) and Comfort (occupied) modes are 

controlled through an external contact by connecting the input 

through a dry contact to signal common. This function may be 

used together with key card switches for hotels or motion 

detectors for offices.

 

FC19 = 3 

Switching Energy Hold OFF 
and Comfort modes 

Opening the input will force the unit into the OFF operation 
mode. The operation mode cannot be overridden by using the 

terminal. Connecting the input to signal common returns 

control of the operation mode to the terminal. This function 

may be used as window contact to prevent loss of energy.  

FC19 = 4 

Heat – Cool changeover 

Switch heating and cooling mode based on supply media or 
outside temperature or binary contact. See below for further 

details.  

FC19 = 5 

Key card with alternative 

setpoint 

As with FC19 = 2, the key card function switches economy 

(unoccupied) and comfort (occupied) modes. Instead of using 

the setpoint shift, the setpoints in unoccupied mode are defined 

by parameter FC21 and FC22. 

 

Configuring auto changeover input if FC19 = 4:  

The auto changeover function automatically changes heating and cooling mode based on supply media 

temperature or outdoor temperature. The difference between the two is in the values of the changeover limits 

FC21 and FC22. See table below for recommended settings. 

Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all signal ground 

levels of involved controllers must be the same in case more than one controller is switched.  

 

Recommended settings for FC21 and FC22: 

Change over mode FC19=4 

Relation FC21 to FC22 

Example FC21 

Example: FC22 

Supply media 

FC21 > FC22 

25°C (77F) 

18°C (64F) 

Outside temperature 

FC21 < FC22 

15°C (59F) 

25°C (77F) 

Dry contact: Heating if contact closed 

FC21 > FC22 

25°C (77F) 

15°C (59F) 

Dry contact: Cooling if contact closed 

FC21 < FC22 

15°C (59F) 

25°C (77F) 

 

 

Summary of Contents for TLC3-FCR-M2-24

Page 1: ...l controller with one control loop The TLC3 FCR M2 is designed for 2 pipe modulating fan coil systems and features 1 NTC temperature sensor input one external passive input for temperature or open con...

Page 2: ...Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive L...

Page 3: ...lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance c...

Page 4: ...t protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection displ...

Page 5: ...d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One ba...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Page 7: ...t points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time pr...

Page 8: ...witched on ON OFF OFF FC 09 Switching delay min running time of fan speed Prevents the fan from switching in too short intervals 0 255 s 10s FC 10 Switching delay min stopping time of fan speed Preven...

Page 9: ...tion detectors for offices FC19 3 Switching Energy Hold OFF and Comfort modes Opening the input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the ter...

Page 10: ...TLC3 FCR M Engineering Manual Doc 70 00 0181 V3 0 Date 20120424 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Reviews: