TLC3-FCR-M Engineering Manual

 

 

Doc: 70-00-0181, V3.0 Date: 20120424 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alteration 

Technical Specification 

Power Supply 

Operating Voltage 

-24 

-230 

 

AC voltage: 50/60Hz 

22-26V AC/DC 

210–250 VAC 

 

Power Consumption 

Max 1W, 1.5 VA 

 

Electrical Connection 

Terminal Connectors 

 

Deluxe type only: Power backup for real time clock 

Min 48h if charged for 24h 

Signal Inputs 

Temperature Inputs 

Range 
Accuracy 

RT Internal, External (Sxx-Tn10 sensor) 
0…50 °C (32…122 °F) 
0.5°C (1°F) 

Signal Outputs 

Digital Switching Outputs 

Switching Type 
AC Switching power 

Insulation strength 

between relays contacts and system electronics: 
between neighboring relays contacts 

DO1 to DO3 
Relays 
2A max. each output 
For -230 types only 
3750V AC to EN 60 730-1 
1250V AC to EN 60 730-1 

 

Analog Outputs 

Output Signal 
Resolution 
Minimum impedance 

AO1, For TLC3-FCR-M4 AO2  
DC 0...10 V 
9.76 mV (10 bit) 
10kOhm, 1mA.  

Environment 

Operation 

Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0°C …50°C (32°F…122°F) 
<95% R.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25°C…70°C (-13°F…158°F) 
<95% R.H. non-condensing 
class 2M2 

Standards 

 

conformity 
EMC Directive 
Low Voltage Directive 

2004/108/EC 
2006/95/EC 

 

Product standards 

Automatic electrical controls for household and similar use 
Special requirement on temperature dependent controls 

 
EN 60 730 –1 
EN 60 730 – 2 - 9 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60 730-1 
Immunity: EN 60 730-1 

 

Degree of Protection 

IP30 to EN 60 529 

 

Pollution Class 

II (EN 60 730-1) 

 

Safety Class:  

for -24 types 
for -230 types 

III (IEC 60 536)  
II (IEC 60 536) 

 

Overvoltage Category:  

for -24 types 
for -230 types 

I (EN 60 730-1) 
III (EN 60 730-1) 

General 

Dimensions (H x W x D)  Front part:  

Power case: 

21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)  
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in) 

 

Material:  

Cover, back part 
Mounting Plate 

ABS plastic (UL94 class V-0) 
Galvanized Steel 

 

Weight (including package)  for -24 types 

for -120 and -230 types 

standard: 260g (9.2oz), deluxe: 270g (9.5oz) 
standard: 295g (10.5oz), deluxe: 305g (10.8oz) 

Dimensions 

 

 

88 (3.5) 

32 (1.3) 

8

8

 (

3

.5

21  

(0.8) 

Space required in flush mounting box: 

(H x W x D)  

60 x 50 x 32mm (2.4 x 2.0 x 1.26 in.) 
 
Distance for mounting screws: 

Horizontal and vertical:  
45 to 63mm (1.8 to 2.5 in.) 
 

Summary of Contents for TLC3-FCR-M2-24

Page 1: ...l controller with one control loop The TLC3 FCR M2 is designed for 2 pipe modulating fan coil systems and features 1 NTC temperature sensor input one external passive input for temperature or open con...

Page 2: ...Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive L...

Page 3: ...lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance c...

Page 4: ...t protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection displ...

Page 5: ...d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One ba...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Page 7: ...t points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time pr...

Page 8: ...witched on ON OFF OFF FC 09 Switching delay min running time of fan speed Prevents the fan from switching in too short intervals 0 255 s 10s FC 10 Switching delay min stopping time of fan speed Preven...

Page 9: ...tion detectors for offices FC19 3 Switching Energy Hold OFF and Comfort modes Opening the input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the ter...

Page 10: ...TLC3 FCR M Engineering Manual Doc 70 00 0181 V3 0 Date 20120424 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...

Reviews: