background image

 

 

TLC3-FCR-M Engineering Manual

 

 

Doc: 70-00-0181, V3.0 Date: 20120424 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

Mounting location 

 

Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of average 

temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 

facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.  

3.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.  

4.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle 

way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is 

normal. Do not use excessive force!  

5.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to 

the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the 

screw too much. 

 

Wiring Diagram 

 

Description:  

Power supply:  

0V Neutral 

Power supply:  

230VAC 

Y1 

Binary output 230V AC:  

Fan speed low 

Y2 

Binary output 230V AC:  

Fan speed medium 

Y3 

Binary output 230V AC:  

Fan speed high 

 

TLC3-FCR-M2: 

 

Signal common:  

Common 0 potential for inputs and analog outputs. 

X1

 

External input: 

NTC 10kΩ @ 25°C (77°F) or open contact to SGND 

U1

 

Analog output:  

0…10 V DC 

 

TLC3-FCR-M4: 

Signal common:  

Common 0 potential for inputs and analog outputs. 

U2

 

Analog cooling output:  

0…10 V DC

  

U1

 

Analog heating output:  

0…10 V DC 

 

X

T INT 

0V 

230V AC 

 

TLC3-FCR-M2 

X1 

X

T EXT

  

IN 

 

U1 

AO1 

 

Y1 

Fan 

Low 

Y2 

Fan 

Med 

Y3 

Fan 

High 

SGND 

 

X

T INT 

0V 

230V AC 

 

TLC3-FCR-M4 

U1 

AO1 

Heat 

 

Y1 

Fan 

Low 

Y2 

Fan 

Med 

Y3 

Fan 

High 

SGND 

 

U2 

AO2 
Cool 

 

Summary of Contents for TLC3-FCR-M2-24

Page 1: ...l controller with one control loop The TLC3 FCR M2 is designed for 2 pipe modulating fan coil systems and features 1 NTC temperature sensor input one external passive input for temperature or open con...

Page 2: ...Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive L...

Page 3: ...lower the front part until the interconnector reaches the mounting plate Continue pressing in a gentle way until the front part is fully connected While inserting the connectors a slight resistance c...

Page 4: ...t protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode will be left once the temperature reaches 10 C 50 F Frost protection displ...

Page 5: ...d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switching event One ba...

Page 6: ...oop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be...

Page 7: ...t points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 04 Enable access to Time pr...

Page 8: ...witched on ON OFF OFF FC 09 Switching delay min running time of fan speed Prevents the fan from switching in too short intervals 0 255 s 10s FC 10 Switching delay min stopping time of fan speed Preven...

Page 9: ...tion detectors for offices FC19 3 Switching Energy Hold OFF and Comfort modes Opening the input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the ter...

Page 10: ...TLC3 FCR M Engineering Manual Doc 70 00 0181 V3 0 Date 20120424 Vector Controls GmbH Switzerland Page 10 Subject to alteration Notes...