TLC-BCR-T Engineering Manual

 

 

Doc: 70-00-0083, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 10 

Configuration parameters for firmware version 2.1 

The TLC-BCR-T can be adapted to wide variety of applications. The adaptation is done with parameters. The 
parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware revision. It is therefore important to use a 
matching product version and parameter set. The firmware version is shown on the large LCD digits when pressing UP 
and DOWN buttons for more than 3 seconds simultaneously.  

Control Parameters (Access Code: 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Parameter Description 

Range 

Standard 

BC 00 

Minimum setpoint limit in Heating mode 

-40…60°C (160°F) 

16°C (61°F) 

BC 01 

Maximum setpoint limit in Heating mode 

-40…60°C (160°F) 

24°C (76°F) 

BC 02 

Minimum setpoint limit in Cooling mode 

-40…60°C (160°F) 

18°C (65°F) 

BC 03 

Maximum setpoint limit in Cooling mode 

-40…60°C (160°F) 

30°C (87°F) 

Controls configuration 

BC 04 

Economy temperature shift 

0…100°C (200°F) 

5.0°C (10°F) 

BC 05 

Switching Span Heating (only used in 2-pipe mode) 

0…100°C (200°F) 

1.5°C (3°F) 

BC 06 

Switching Span Cooling (only used in 2-pipe mode) 

0…100°C (200°F) 

1.0°C (2°F) 

BC 07 

Switching Hysteresis 

0…100°C (200°F) 

0.5°C (1°F) 

BC 08 

Parameter not used 

ON, OFF 

OFF 

BC 09 

Delay OFF (Minimum running time) 

0…255s 

10s 

BC 10 

Delay ON (Minimum stopping time) 

0…255s 

10s 

BC 11 

2-pipe or 4-pipe system: OFF = 2-pipe, ON = 4-pipe system 

ON, OFF 

ON 

BC 12 

Dead zone between heating & cooling set point X

DZ

 

0…100°C (200°F) 

1.0°C (2°F) 

BC 13 

Delay on Heat/Cool change over 

0…255 min 

5 min 

Output configuration 

BC 14 

Output setting, Binary or 3-point:  
OFF = Binary (DO1 Heating, DO2 Cooling) 
ON = 3-point output (DO1 OPEN, DO2 CLOSE) 

ON, OFF 

OFF 

BC 15 

Reversing valve in binary mode (only for 4-pipe system. BC11 = ON) 
0 = no reversing valve  
1 = reversing valve while heating  (DO1 Rev Valve, DO2 Stage 1) 
2 = reversing valve while cooling  (DO1 Stage 1, DO2 Rev Valve) 

0...2 0 

BC 16 

Running Time in 3-point mode 

0…255 s 

90 s 

Input configuration 

BC 17 

External input:  
0 = No external input 
1 = External temperature sensor 
2 = Occupation sensor – Comfort / Economy 
3 = Occupation sensor – Comfort / Off 
4 = Heat / Cool change by open contact. Contact open = Heat 
5 = Heat / Cool change by open contact. Contact open = Cool 
6 = Auto-changeover based on supply temperature 
7 = Auto-changeover based on outside temperature 
8 = Key card with alternative setpoint 

0…8 0 

BC 18 

Activation delay (Minutes) = the time the binary input needs to be open 
before economy/off mode is activated. 

0…255 min 

5 min 

BC 19 

Auto-changeover limit cooling for supply temperature FC11 = 6 
Auto-changeover limit heating for outside temperature FC11 = 7 
or economy setpoint in heating mode if BC17 = 8 

-40…60°C (160°F) 

16°C (61°F) 

BC 20 

Auto-changeover limit heating for supply temperature FC11 = 6 
Auto-changeover limit cooling for outside temperature FC11 = 7 
or economy setpoint in cooling mode if BC17 = 8 

-40…60°C (160°F) 

28°C (83°F) 

 

 

Subject to alteration 

Summary of Contents for TLC-BCR-T

Page 1: ...diator control chilled ceiling floor heating Simple individual room control for hotel rooms meeting rooms etc General Description The TLC BCR T is a stand alone electronic binary controller with one c...

Page 2: ...Design and Installation The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS pl...

Page 3: ...re sensor or open contact 6 GND Signal Ground Subject to alteration Space required in flush mounting box H x W x D 60 x 50 x 30mm 2 4 x 2 0 x 1 2 in Distance for mounting screws Horizontal and vertica...

Page 4: ...wered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 4...

Page 5: ...ture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually ac...

Page 6: ...UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small digits Pressing the OPTION button will enter the clock setup The minutes ar...

Page 7: ...the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Sett...

Page 8: ...to reduce the startup load of large motors multiple stages will be switched on and off step by step Binary Control T Room Temperature wH Setpoint Heating Mode DZ Dead Zone QH Offset Heating wC Setpoi...

Page 9: ...mperature of the supply media Connect a qualified passive sensor to the external input Heating mode is activated once the supply temperature is above the heating limit Cooling is activated when the su...

Page 10: ...imum running time 0 255s 10s BC 10 Delay ON Minimum stopping time 0 255s 10s BC 11 2 pipe or 4 pipe system OFF 2 pipe ON 4 pipe system ON OFF ON BC 12 Dead zone between heating cooling set point XDZ 0...