TLC-BCR-T Engineering Manual

 

 

Doc: 70-00-0083, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 2 

Technical Specification 

Power Supply 

Operating Voltage 

190 – 250 V AC 50/60 Hz 

 

Power Consumption 

Max 1W, 1.5 VA 

 

Electrical Connection 

Terminal Connectors 

 

Fuse 

3A, 250VAC (Warranty void if replaced) 

 

Deluxe type only: 
Power backup for real time clock 

 
Min 48h if charged for 24h 

Signal Inputs 

Temperature Inputs 

Range 
Resolution 
Accuracy 

RT Internal, external 
-40°C…70°C (-40°F to 158°F) 
0.1°C (0.1°F) 
0.5°C (1°F) 

Signal Outputs 

Digital Switching Outputs 

Switching type 
AC Switching power 

DO1…DO2 

Relays 
2(1.2) A, 250VAC (max fan power 300W) 

Environment Operation 

Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0°C …50°C (32°F…122°F) 
<95% R.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 
-25°C…0°C (-13°F…158°F) 
<95% R.H. non-condensing 
class 2M2 

Standards 

 

conform according to  
EMC Standard 89/336/EEC 
EMEI Standard 73/23/EEC 

 
EN 61 000-6-1/ EN 61 000-6-3 

 

Product standards 

Automatic electrical controls for 
household and similar use 
Special requirement on 
temperature dependent controls 

 
EN 60 730 –1 
 
EN 60 730 – 2 - 9 

 

Degree of Protection 

IP30 to EN 60 529 

 

Safety Class 

II (IEC 60536) 

General 

Dimensions (H x W x D) 

Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)  
Power case: 60 x 50 x 30mm (2.4 x 2.0 x 1.2 in.) 

 

Weight (including package) 

260g 

 
Mechanical Design and Installation 

The unit consists of three parts:  

1.

 

The mounting plate made of galvanized steel.  

2.

 

The power case made of fire proof ABS plastic.  

3.

 

The front part made of white fire proof ABS plastic.  

Installation 

1.

 

Arrange the wires to be connected and cut them to equal length.  

2.

 

Connect them to the terminals of the power case according to wiring diagram 

3.

 

Clip the power case to the mounting plate, pull the connection cable through the large central opening of the 

mounting plate. Insert the power case into the flush mounting box. Carefully arrange power wires.  

4.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 

facing to the ground. Make sure the screw heads do not stand out more than 5 mm of the surface of the 
mounting plate.  

5.

 

Connect the connection cable to the plug located on the back of the front part. 

6.

 

Slide the two latches located on the top of the front part into the hooks of the mounting plate.  

7.

 

Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make sure 

the connection cable does not get into the way. 

8.

 

Tighten the front holding screw to secure the front part to the mounting plate.  

Mounting location 

 

On an easy accessible interior wall, approx. 1.5 m above the floor in an area of average temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical 
equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

 

Summary of Contents for TLC-BCR-T

Page 1: ...diator control chilled ceiling floor heating Simple individual room control for hotel rooms meeting rooms etc General Description The TLC BCR T is a stand alone electronic binary controller with one c...

Page 2: ...Design and Installation The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS pl...

Page 3: ...re sensor or open contact 6 GND Signal Ground Subject to alteration Space required in flush mounting box H x W x D 60 x 50 x 30mm 2 4 x 2 0 x 1 2 in Distance for mounting screws Horizontal and vertica...

Page 4: ...wered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 4...

Page 5: ...ture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually ac...

Page 6: ...UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small digits Pressing the OPTION button will enter the clock setup The minutes ar...

Page 7: ...the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Sett...

Page 8: ...to reduce the startup load of large motors multiple stages will be switched on and off step by step Binary Control T Room Temperature wH Setpoint Heating Mode DZ Dead Zone QH Offset Heating wC Setpoi...

Page 9: ...mperature of the supply media Connect a qualified passive sensor to the external input Heating mode is activated once the supply temperature is above the heating limit Cooling is activated when the su...

Page 10: ...imum running time 0 255s 10s BC 10 Delay ON Minimum stopping time 0 255s 10s BC 11 2 pipe or 4 pipe system OFF 2 pipe ON 4 pipe system ON OFF ON BC 12 Dead zone between heating cooling set point XDZ 0...