background image

 

 

TLC-BCR-T Engineering Manual

 

 

Doc: 70-00-0083, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 5 

Clock Operation and Time Schedules (Deluxe Version) 

TLC-BCR-T-D contains a real time clock. Up to 16 mode changes (not defined, Off, Economy, Comfort, University mode) 
based on weekdays and time may be programmed. See chapter operation on how to program switch times.  
The different scheduled mode changes have these effects: 

Name on display 

Function 

Override reset 

no 

Switching event not used 

 

OFF 

Operation mode changes to off mode 

Reset is active 

ECO 

Operation mode changes to economy mode 

Reset is not active 

ON 

Operation mode changes to comfort mode 

Reset is not active 

UNI 

Operation mode does not change  

Reset is not active 

 
UNI: University mode: This switching mode is used for rooms such as lecture rooms and auditoriums that might be 
occupied during a certain time. During this time the reset is not active. The unit will not start itself when UNI mode is 
active. It still needs to be manually activated. This is to avoid unnecessary heating or cooling of such rooms while they 
are not occupied.  
Override reset function: The override reset applies when the unit is manually switched on, while in scheduled off mode. 
The unit will switch automatically off when the reset time defined in UP13 expires. Setting UP13 to 0, disables the 
override reset.  
A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined. See 
chapter operation, advanced settings for instructions on how to set the time. 

Error messages 

The TLC-BCR-T may display the following error condition:  
Err1: 

Temperature sensor faulty. The temperature sensor is damaged.  

Err2: 

External input for heat / cool auto change over missing or damaged.  

FP: 

Frost protection is active.  

Summary of Contents for TLC-BCR-T

Page 1: ...diator control chilled ceiling floor heating Simple individual room control for hotel rooms meeting rooms etc General Description The TLC BCR T is a stand alone electronic binary controller with one c...

Page 2: ...Design and Installation The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS pl...

Page 3: ...re sensor or open contact 6 GND Signal Ground Subject to alteration Space required in flush mounting box H x W x D 60 x 50 x 30mm 2 4 x 2 0 x 1 2 in Distance for mounting screws Horizontal and vertica...

Page 4: ...wered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 4...

Page 5: ...ture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually ac...

Page 6: ...UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small digits Pressing the OPTION button will enter the clock setup The minutes ar...

Page 7: ...the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Sett...

Page 8: ...to reduce the startup load of large motors multiple stages will be switched on and off step by step Binary Control T Room Temperature wH Setpoint Heating Mode DZ Dead Zone QH Offset Heating wC Setpoi...

Page 9: ...mperature of the supply media Connect a qualified passive sensor to the external input Heating mode is activated once the supply temperature is above the heating limit Cooling is activated when the su...

Page 10: ...imum running time 0 255s 10s BC 10 Delay ON Minimum stopping time 0 255s 10s BC 11 2 pipe or 4 pipe system OFF 2 pipe ON 4 pipe system ON OFF ON BC 12 Dead zone between heating cooling set point XDZ 0...