TCY-MZ 

Display and operation 

 

Doc: 70-00-0311 V1.0, 2012-11-09 

© Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

www.vectorcontrols.com 

Display and operation 

 

Operation Modes 

STEP 

Normal mode 

The ventilation is operating based on selected values 

OFF 

Absence mode 

Ventilation is operated with on and off intervals. The intensity and 

duration of both on and off intervals may be defined with 

parameters. The default is 5.5 hours in off mode and 0.5 hours 

with minimum airflow.   

 

Party mode (FULL) 

Ventilation is fully activated. The reset time is shown on the 

display. It may be set.  

HIGH 

Full supply mode 

This mode is activated by an external input for example a switch 

on the kitchen or bathroom exhaust fan. The Supply air opens full 

and the return air is switched off. The values of full supply mode 

for both supply and return air are selectable through parameters.   

 

Time schedule mode 

Airflow is defined by time schedules 

 

Manual override 

Short term manual override of the time schedule value. After a 

fixed reset time of 60 min the positioner will revert to the 

scheduled value.  

Power Failure 

All the parameters and set points are memorized and do not need to be reentered. Depending on 

UP03

 the unit will 

remain switched off, switch on automatically or return to the operation mode it was in before the power failure. 

Deluxe version only

: Timer operation and daytime setting will be retained for 24h. The controller has to be connected to a 

power supply for at least 10 hours for the backup function to operate accordingly.  

 

 

 

Left Key 

Short press activates party mode.  
Long press activates absence 
mode.   
(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 

Upper Key 

Increases airflow or reset time 

(Parameter setting: SCROLL 
menu options and 
parameters) 

Lower Key 

Decreases airflow or reset time 

(Parameter setting: SCROLL menu options 
and parameters) 

Mode 

Display of operation 

mode 

 
 

Large Digits 

Display of input or parameter 
value. 

Indicators 

1 External input closed 

(Parameter settings: 

8,9,10: Value may be 

changed) 

Vertical Bar 

(scrolls up/down, 10% resolution) 

Small Digits 

Display of setpoint, clock or 
parameter number. 

Right Key  

Long press >2 sec: Adjustment for clock 
and time schedules (for –D Versions) 

Short Press: Toggling of manual and time 
schedule operation modes(for –D Versions) 

(Parameter setting: ENTER to select menu 
option, accept parameter) 

Summary of Contents for TCY-MZ

Page 1: ...pplications Control of ventilation systems for comfort and industrial applications General description The TCY MZ is a microprocessor controlled precision positioner with real time clock and time sche...

Page 2: ...H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class...

Page 3: ...wall approx 1 5 m 4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight Installation 1 Connect the wires to be connected to the terminals of the power case according...

Page 4: ...alue Power Failure All the parameters and set points are memorized and do not need to be reentered Depending on UP03 the unit will remain switched off switch on automatically or return to the operatio...

Page 5: ...ec SEL and current time displayed Press UP SEL and PRO displayed clock symbol blinks Press RIGHT Time schedule status displayed OFF or ON Press RIGHT OFF ON blinks UP DOWN to change OPTION to save SEL...

Page 6: ...ect a password using UP or DOWN buttons Select 009 in order to get access to the user parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediate...

Page 7: ...OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 100 CP 12 Full supply mode Volume for return air OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 OFF Signal limitation for VAV systems The...

Reviews: