background image

 

TCY-MZ 

Configuration 

 

Doc: 70-00-0311 V1.0, 2012-11-09 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

www.vectorcontrols.com 

Control Functions (Password 241) 

Warning! Only experts should change these settings! See user parameters for login procedure  

Parameter  Description 

Range 

Default 

CP 00 

Signal type: OFF = 0…10V, ON = 2-10V 

OFF, ON 

ON (2-10V) 

CP 01 

Min output for AO1 (TCY-MZ2 = Supply air) 

0 – 100 % 

0% 

CP 02 

Max output for AO1 (TCY-MZ2 = Supply air) 

0 – 100 % 

100% 

CP 03 

Min output for AO2 (TCY-MZ2 = Return air)  

0 – 100 % 

0% 

CP 04 

Max output for AO2 (TCY-MZ2 = Return air) 

0 – 100 % 

100% 

CP 05 

Absence mode: High time 

0…25.5h 

0.5h 

CP 06 

Absence mode: Low time 

0…25.5h 

5.5h 

CP 07 

Absence mode: Output during high time.  
OFF = 0V(energy hold off) , 0…100% 0-10V or 2-10V 

OFF, 0 – 100 % 

0% 

CP 08 

Absence mode: Output during low time.  

OFF = 0V(energy hold off) , 0…100% 0-10V or 2-10V 

OFF, 0 – 100 % 

OFF 

CP 09 

Configuration of external input (X1) 

0 = Disabled  

1 = Normal Absence mode changeover 

2 = Full supply mode control 

0…2 

CP 10 

Activation delay (seconds): 
If CP 09 = 1: The time the binary input needs to be open 

before absence mode is activated.

 

If CP 09 = 2: The time the binary input needs to be connected 
to signal ground before full supply mode is activated.  

0…1275s 

60s 

CP 11 

Full supply mode: Volume for supply air 

OFF = 0V (energy hold off), 0…100% 0-10V or 2-10V 

OFF, 0…100% 

100% 

CP 12 

Full supply mode: Volume for return air 

OFF = 0V (energy hold off), 0…100% 0-10V or 2-10V 

OFF; 0…100% 

OFF 

 

Signal limitation for VAV systems 

The minimum and maximum airflow limits may be adjusted directly on the controller. A setup on the VAV 

actuator is thus not required.  

 

Absence mode 

The ventilation is activated during absence mode in selectable intervals. High and Low time as well as high and 

low levels of the absence mode may be defined. Per default a low time of 5.5 hours with energy hold off level is 

followed by a high time of 0.5hours with minimum air flow. During energy hold off level, the ventilation is off.  

 

Configuring the function of the external input X1 

 

Normal – Absence mode changeover 

The operation mode can be controlled through an external contact. If the contact is closed (input connected to 

signal ground), normal mode is activated. If the contact is open for a time defined in CP10, absence mode is 

activated. Pressing the LEFT button reactivates normal mode and resets the countdown timer defined with CP10. 

A possible application is a motion detector for an office or meeting room in series with a window contact.  

 

Full supply mode 

If the contact closes, the supply air will be set to maximum (defined in CP11) and the return air set to OFF 

(CP12). This function is used for kitchen exhaust or bathroom exhaust fans to prevent negative indoor pressure.  

A delay may be defined with CP10.  

Summary of Contents for TCY-MZ

Page 1: ...pplications Control of ventilation systems for comfort and industrial applications General description The TCY MZ is a microprocessor controlled precision positioner with real time clock and time sche...

Page 2: ...H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class...

Page 3: ...wall approx 1 5 m 4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight Installation 1 Connect the wires to be connected to the terminals of the power case according...

Page 4: ...alue Power Failure All the parameters and set points are memorized and do not need to be reentered Depending on UP03 the unit will remain switched off switch on automatically or return to the operatio...

Page 5: ...ec SEL and current time displayed Press UP SEL and PRO displayed clock symbol blinks Press RIGHT Time schedule status displayed OFF or ON Press RIGHT OFF ON blinks UP DOWN to change OPTION to save SEL...

Page 6: ...ect a password using UP or DOWN buttons Select 009 in order to get access to the user parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediate...

Page 7: ...OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 100 CP 12 Full supply mode Volume for return air OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 OFF Signal limitation for VAV systems The...

Reviews: