background image

 

TCY-FT-U 

Configuration 

 

Doc: 70-00-0128B, V1.2, 20110621 

© Vector Controls GmbH, Switzerland 

Page 6 

Subject to alteration 

Control Functions (Password 241) 

Warning! Only experts should change these settings! See user parameters for login procedure.  

Control configuration 

Parameter Description 

Range 

Default 

CP 00 

Minimum setpoint limit in heating mode 

0-60°C (32-160°F) 

16°C (61°F) 

CP 01 

Maximum setpoint limit in heating mode 

0-60°C (32-160°F) 

30°C (86°F) 

CP 02 

Minimum setpoint limit in cooling mode 

0-60°C (32-160°F) 

18°C (65°F) 

CP 03 

Maximum setpoint limit in cooling mode 

0-60°C (32-160°F) 

30°C (86°F) 

CP 04 

Economy (unoccupied) Mode temperature shift: 
The comfort (occupied) setpoint is shifted by the value set 
with parameter. If heating is active the comfort setpoint will 
be decreased, if cooling is active, the setpoint will be 
increased. (Enable with UP06.)  

0-100°C (200°F) 

5.0°C (10°F) 

CP 05 

Dead Zone Span (TCY-FT4-U only):  
The Dead Zone Span lies between the heating and the cooling 
setpoint. The output is off while the temperature is within the 

dead zone span. A negative dead zone is not possible. 

0-100°C (200°F) 

1.0°C (2°F) 

CP 06 

Heat/Cool Changeover Delay (TCY-FT4-U only): 
A demand to switch between heating and cooling must persist 
for the length of time set with this parameter before the 
controller switches. Prevents activation of a sequence during a 
short-term change in temperature in order to protect 
equipment (with control overshoot for example)  

0-255 min 

5 min 

CP 07 

P-band heating X

PH

 

0-100°C (200°F) 

2.0°C (4.0°F) 

CP 08 

P-band cooling X

PC

 

0-100°C (200°F) 

2.0°C (4.0°F) 

CP 09 

K

IH

, Integral gain heating, in 0.1 steps, (TI is fixed to 4s) 

0 disables ID part 
low value = slow reaction 

high value = fast reaction 

0…25.5 0.0 

CP 10 

K

IC

, Integral gain cooling, in 0.1 steps, 0 disables I part 

0…25.5 

0.0 

CP 11 

Configuration of operation mode 
0 = TCY-FT2-U-W1 = Cooling only

 

1 = TCY-FT2-U-W2 = Heating only

 

2 = TCY-FT2-U = Heating and Cooling (2 pipe system) 

3 = TCY-FT4-U = Heating and Cooling (4 pipe system) 

TCY-FT2-U: 0 - 2 

TCY-FT4-U: 0 – 3 

TCY-FT2-U-W1:  0 
TCY-FT2-U-W2:  1 
TCY-FT2-U:  

TCY-FT4-U:  

Î

 

Proportional control

 

(P-band)  

The proportional control function calculates the output based on the difference between setpoint and measured value. 
The proportional band (P-band) defines the difference between setpoint and measured value which will result in a 100% 
output. For example, with a heating or reverse 0-10v control sequence, and a 2.0°C (4.0°F) P-band value, at 10v the 
controller will be 2.0°C (4.0°F) below setpoint. This is the working range of the proportional control sequence. 

Setting the proportional band to 0 disables proportional control. 

 

Î

 

Integral and Differential control

  

Proportional control is a very stable control mode. The flaw of proportional control alone, however, is that the setpoint 
is normally not reached. As the measured value gets closer to the setpoint, the output reduces until it reaches a point, 
a fraction above or below the setpoint, where the output equals the load. To reach the setpoint and achieve a higher 
level in comfort the Integral/Differential function should be activated.  

Integral Gain (KI) 

dynamically increases the output by the selected KI value until the setpoint is reached. The 

challenge, however, is to prevent hunting, where the output increases too fast, the temperature overshoots the 
setpoint, the output goes to 0, the temperature undershoots the setpoint, and the cycle repeats itself. Hunting may 
result if the integral gain

 

is too high. Each system is different. It is recommended to start with a KI value of 0.5 for 

water based systems and 1.0 for air based systems. Reduce this value if the measured value overshoots the setpoint 
by more than 1°C (2°F). Increase the value if the output takes too long to reach the setpoint. Air based systems 
react faster than water based systems.  

Setting the integral gain to 0 disables integral and differential control.  

 

Summary of Contents for TCY-FT2-U-W01

Page 1: ...No special tool or software is required Name Ordering Item Name Item code Control Type Key data TCY FT2 U W01 40 10 0068 1 Cooling only Compact PID controller with 2 TI 1 3 point output TCY FT2 U W02...

Page 2: ...condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 S...

Page 3: ...ation of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install th...

Page 4: ...o a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY FT U may display the following error condition Err1 The connection to the temperature senso...

Page 5: ...using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displa...

Page 6: ...1 Cooling only 1 TCY FT2 U W2 Heating only 2 TCY FT2 U Heating and Cooling 2 pipe system 3 TCY FT4 U Heating and Cooling 4 pipe system TCY FT2 U 0 2 TCY FT4 U 0 3 TCY FT2 U W1 0 TCY FT2 U W2 1 TCY FT2...

Page 7: ...open 0 255s 90s CP 14 Minimum running time FO1 TCY FT4 U heating output The minimum time the output runs once it starts This setting prevents frequent switches with very short running times 0 255s 3s...

Page 8: ...offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the t...

Reviews: