background image

 
 

Chapter 6

 

 

Aluminum H-, F- and B-Type Evaporators 

(Horizontal, Flat, Bin Type)

 

 

6:1 

Location

 

All types of evaporator need to be located as high as possible in the icebox to maintain the correct 
temperatures, with consideration being given to access to the interior freezing section in the H and B- 
type. 

Special attention must be given to the fact that air flow must be allowed to circulate to and 

from the rear of the evaporator plate.

 This necessitates leaving a gap of approximately 1” between 

the top of the evaporator and the roof of the box, and similar spacing at the lower edge. In conjunction 
with this, it is important that the ¾” spacers provided be used to offset the evaporator on all points 
from the icebox wall. Additional spacers may be fashioned from wood, hose, or similar material, if 
required. 
 
The H- and B-types may be mounted in any position. The F-type 

must

 be mounted with the indicator 

arrows pointing upwards, on a vertical wall, and with the refrigerant channels running in a horizontal 
orientation. 
 
Do not alter the orientation of the tubing and/or tubing components secured to the end of the 
evaporator plate. Do not remove any securing zip ties, or attempt to straighten the tubing.

 

 
6:2 

Bending Instructions for flat plates: 

The F-type flat evaporators may be carefully bent on a minimum 1.5" radius to follow the shape of the 
icebox. This is best done by holding a section of suitably padded PVC pipe (with an outside diameter 
of 3.0" or greater) firmly down on the plate, and then carefully bending the section upwards with the 
palm of your hand. The stainless steel plates need more force to bend and may require the assistance of 
a second person. This must be done slowly and with great care to avoid excessive kinking of the 
channels in the evaporator. Never attempt to bend a plate downwards over a pipe, as damage may 
result. The area to be bent should be warmed with a hair dryer or heat gun to approximately 200

before bending, in order to prevent the paint from cracking. There are sections of the evaporator that 
must not be bent, and these are indicated on the Bending Sheet included with the evaporator. If the 
Bending Sheet has been misplaced, a replacement can be obtained from Coastal Climate Control. 
 

All F-type evaporators can be mounted with either side facing inwards, including the 380F 

which has one smooth side and one with channels. F-type plates with a stainless steel cover must be 
mounted with the stainless side facing inwards. 

 
6:3 

Installation

 

All evaporators have approximately 9' of copper tubing attached, 

with dust-plugs in the end 

fittings that must remain installed until the very last moment when the connections are ready 
to be made.

 A 1.5" hole needs be drilled in the wall of the icebox, as high as possible, and 

through successive bulkheads, as required. Carefully unroll the tubing, feeding it through the 
holes to the area where the compressor/condenser is located. Any bends that need to be 
fashioned in the tubing must be made carefully with as large a radius as possible to avoid kinking. 
 

Excess tubing should be carefully coiled up 

outside of the box

 and fastened out of the way in a 

horizontal orientation. 

One tube is made intentionally longer than the other to enable as small a 

hole as possible to be made in the box wall, bulkheads, etc. and this allows the couplings to be fed 
through one after the other. When the tubing run is complete, carefully fashion the longer tube so 
that the two halves of the coupling can be easily connected. Some evaporators have fragile 
sections of aluminum tubing close to the body of the evaporator that must be handled very 
carefully. Warnings to that effect are attached to the evaporators in question.

 

Summary of Contents for Frigoboat Capri 35F

Page 1: ...s Air Cooled Pumped Water Cooled Keel Cooled and Keel plus Air Cooled Systems using Secop formally Danfoss BD 35 or BD 50 compressors It is important to read this manual thoroughly before installing a...

Page 2: ...it or an Air Add On air cooled condenser is installed together with a Keel Cooler ensure that the fan is operated only when the boat is out of the water and then switched off when the boat is launched...

Page 3: ...Capri 35F Capri 50F Air cooled These units are designed to be mounted with compressor right way up on a horizontal surface in areas where they will not be susceptible to physical or water damage but...

Page 4: ...ll deliver 12v even if the system is connected to a 24v supply Full wiring instructions are included with the compressor If more than one W35 or W50 is sharing a single water pump they must be plumbed...

Page 5: ...ion of the transom that is below the waterline when at rest Keep the two tubes from the Keel Cooler separate from each other and do not insulate them It is extremely important to orientate the cylindr...

Page 6: ...control running at 2000 RPM All others must have either a manually adjustable compressor speed controller like a Speed Board or alternatively an automatic smart speed control such as the Merlin II Sma...

Page 7: ...to the controller there may be a delay of up to 30 seconds before the compressor starts Note 2 If initial power is applied that is above the low voltage threshold but below the cut in voltage value se...

Page 8: ...els in the evaporator Never attempt to bend a plate downwards over a pipe as damage may result The area to be bent should be warmed with a hair dryer or heat gun to approximately 200 F before bending...

Page 9: ...lastic plate on the evaporator so that it lays in the special grooves of the plastic plate Finish by tightening the clamping screw If using the Coastal MK3 digital thermostat the sensor mounts on the...

Page 10: ...refully coiled up and secured out of the way to avoid damage When securing the sensing tube make sure contact is made only with the evaporator at the point where it is attached under the plastic mount...

Page 11: ...top of the barrier 1 should be sufficient or 3 or more holes of the same size as the one behind the spillover fan All other holes gaps etc in the barrier must be completely sealed including drains 8...

Page 12: ...talled until the very last moment when you are ready to connect the system together Once the dust caps have been removed it is imperative that the exposed components and surfaces be kept free of dust...

Page 13: ...tion Use either a breaker or fast blow fuse with 15 amp rating for a 12v supply or 7 5 amp for 24v 10 4 Connections Power Connect the power supply to the controller on the top two terminals using slip...

Page 14: ...factory installed on the terminals marked F Black or Blue and Red If the wires are reversed the fan will not run The K50F and W50F models have a small oil cooler fan installed Full instructions are i...

Page 15: ...oller or compressor to be faulty Controller can be removed by unscrewing the retaining screw or by levering the plastic case over the screw head 11 1 Compressor not running no start attempt Probable c...

Page 16: ...ty or inadequate power supply Most likely Monitor the supply voltage at the power terminals on the controller before during and after start attempts to ensure that it does not fall below threshold lev...

Page 17: ...ng in others the system may be low on refrigerant or overcharged Call Veco NA for advice or go to www veco na com Technical Information 7 Drain left unplugged If your icebox is equipped with a drain i...

Page 18: ...lation 11 5 Excessive frost build up Note This is the result of moist air being allowed to enter the box Problems are compounded when cold dense air leaks from the lower area of the box through an ope...

Page 19: ...cation Acts of God or service by personnel other than those pre authorized by the Company Damage failure or malfunction resulting from inadequate or faulty power supply to the system or improper fault...

Reviews: