pressure relief valve and associated shut-off 

valves in good working order. Empty recovery 

cylinders are evacuated and, if possible, cooled 

before recovery occurs. The recovery equipment 

shall be in good working order with a set of instruc-

tions concerning the equipment that is at hand and 

shall be suitable for the recovery of flammable 

refrigerants. In addition, a set of calibrated weigh-

ing scales shall be available and in good working 

order. Hoses shall be complete with leak-free 

disconnect couplings and in good condition. 

Before using the recovery machine, check that it is 

in satisfactory working order, has been properly 

maintained and that any associated electrical 

components are sealed to prevent ignition in the 

event of a refrigerant release. Consult manufactur-

er if in doubt.
The recovered refrigerant shall be returned to the 

refrigerant supplier in the correct recovery cylinder, 

and the relevant Waste Transfer Note arranged. Do 

not mix refrigerants in recovery units and especial-

ly not in cylinders.
If compressors or compressor oils are to be 

removed, ensure that they have been evacuated to 

an acceptable level to make certain that flamma-

ble refrigerant does not remain within the 

lubricant. The evacuation process shall be carried 

out prior to returning the compressor to the suppli-

ers. Only electric heating to the compressor body 

shall be employed to accelerate this process. 

When oil is drained from a system, it shall be 

carried out safely.
Fuse parameters of the machine
Type: 5H or 524 Voltage: 250V Current: 3.15 A
 

7

7

PERMISSIBLE EXCESSIVE OPERATING PRESSURE

Suction.........................................................................................................................0.6MPa(6Kgf/cm

2

Discharge...................................................................................................................2.5MPa(25Kgf/cm

2

Maximum Operation Pressure................................................................................................4.0MPa(40Kgf/cm

2

Dimension (W x D x H ) mm.......................................................................................................360Wx246Dx506H 
Applicable temperature..........................................................................................................................5°C-35°C 
Water Tank Capacity.....................................................................................................................................3.2 L

SPECIFICATIONS

Power Supply
Power Input
Moisture Removal 
Refrigerant

Model REF 636134

(30°C RH80%)

220-240V~50Hz

365 W

30 liters/day

R290, 0.13kg

EN

Ref. 636134

DEHUMIDIFIER

DESHUMIFICADOR

TRANSPORTATION, MARKING AND STORAGE FOR UNITS
1. Transport of equipment containing flammable refrigerants. 

Compliance with the transport regulations. 
2. Marking of equipment using signs. Compliance with local regulations.
3. Disposal of equipment using flammable refrigerants. 

Compliance with national regulations. 
4. Storage of equipment/appliances. The storage of 

equipment should be in accordance with the manufacturer’s 

instructions. 
5. Storage of packed (unsold) equipment. Storage package 

protection should be constructed such that mechanical 

damage to the equipment inside the package will not cause a 

leak of the refrigerant charge. The maximum number of 

pieces of equipment permitted to be stored together will be 

determined by local regulations.   
6.  The appliance shall be stored so as to prevent mechanical 

damage from occurring.
7.  General work area.  All maintenance staff and others 

working in the local area shall be instructed on the nature of 

work  being carried out. Work in confined spaces shall  be 

avoided. The area around the workspace shall be sectioned 

off. Ensure that the conditions within the area have been 

made safe by control of flammable material.

This marking indicates that this product should not be disposed with other household 

wastes throughout the EU. 
To prevent possible hazards to the environment or human health from uncontrolled waste 

disposal, please recycle it to prove the sustainable reuse of material resources. Please ask 

return and collection systems or contact the retailer where the product was purchased to 

return your used device, they can recycle products safely.

Summary of Contents for 636134

Page 1: ...ER USER S MANUAL MANUAL DEL USUARIO Please read this manual before use Porfavor leer el manual antes de usar Distribuido por HORTICULTURA T CNICA S L U CIF B97303937 C AIG ADERS N 4 46680 ALGEMESI VAL...

Page 2: ...m power supply before moving or cleaning the product and also when the product is not in used 14 Please operate the product with specified electricity voltage 15 Please use this product only for house...

Page 3: ...nit the unit is set to be continuous dehumidification CO When ambient humidity is lower than setting humidi ty by 3 compressor will stop automatically and return working until the ambient humidity is...

Page 4: ...to let water flow out FILTER REMOVAL 1 Take out the water tank before remove the filter 2 Pulling out the filter with handles of filter 3 Wash the filter with cool water cooler than 40 C every two wee...

Page 5: ...ately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carried out The ventilation should safely disperse...

Page 6: ...ffects of aging or continual vibration from sources such as compressors or fans 5 DETECTION OF FLAMMABLE REFRIGERANTS Under no circumstances shall potential sources of ignition be used in the searchin...

Page 7: ...re attempting the procedure ensure that Mechanical handling equipment is available if required for handling refrigerant cylinders All personal protective equipment is available and being used correctl...

Page 8: ...f cm2 Dimension W x D x H mm 360Wx246Dx506H Applicable temperature 5 C 35 C Water Tank Capacity 3 2 L SPECIFICATIONS Power Supply Power Input Moisture Removal Refrigerant Model REF 636134 30 C RH80 22...

Page 9: ...a causar da os a los usuarios 13 Desconecte el electrodom stico de la fuente de alimentaci n antes de moverlo o limpiarlo y tambi n cuando el producto no se utilice 14 Utilice el producto con la tensi...

Page 10: ...a humedad relativa 50 60 70 u 80 modo de confort AU y otra vez a deshumidificaci n contin uada CO La primera vez que la encienda la unidad est configurada en el modo de deshumidi ficaci n continuada...

Page 11: ...e PVC El tubo de PVC no se incluye con el producto USO DEL DEP SITO DE AGUA Cuando el producto est deshumidificando el agua que se condense puede drenarse en el dep sito de agua Cuando el dep sito de...

Page 12: ...dante Antes de comen zar el trabajo la zona adyacente al equipo se debe inspeccionar para descartar la presencia de peligros inflamables o riesgos de ignici n Deber n ponerse carteles de Prohibido fum...

Page 13: ...uso de silicona sellante puede mermar la eficacia de algunos equipos de detecci n de fugas No es preciso aislar los componentes con seguridad intr nseca antes de trabajar en ellos 3 REPARACI N DE LOS...

Page 14: ...la bomba de vac o no est cerca de ninguna fuente de ignici n y de que la zona est bien ventilada 8 PROCEDIMIENTOS DE CARGA Adem s de los procedimientos de carga conven cionales deben cumplirse los req...

Page 15: ...rante es decir deben ser cilindros especiales para la recuperaci n de refrigerante Los cilindros deben contar con una v lvula de alivio de presi n y con v lvulas de cierre en buen estado Los cilindros...

Page 16: ...UNIDADES 1 Transporte de equipo que contenga refrigerantes inflamables Cumplimiento de las normas de transporte 2 Marcado del equipo mediante se ales Cumplimiento de la normativa local 3 Eliminaci n d...

Reviews: