* Fan control settings

The 

ALFANET 95

 has various adjustment possibilities for  the Fan. Normally, the fan is always running

unless one of the parameters below is set at 1:

Parameter 20 = 1: 

Fan switch differential active.

The  fan  runs  only  if  the  temperature  of  the  defrost  sensor  is  lower  than  the  control  sensor
temperature minus the temperature of the switch differential fan (P21)
 {Fan on if  T

defrost 

< (T

control 

- T

fandiff.

)}.

Parameter 25,26:

Fan switching on delay after defrosting.

To prevent the fan from running immediately after defrosting and draining of the evaporator and
thus blowing warm air into the cell, the following two conditions can be set;
a. The fan is blocked until the defrost-sensor measures a temperature that is lower than the set

switch-on temperature of  the fan (P25).

b. The fan is blocked until the switch-on delay of  the fan (P26) is passed. When the defrost-

sensor reaches the switch-on temperature (P25) within the switch-on delay, then the fan is
released again.

Parameter 22 = 1:

Fan is off, when the compressor is off.

The fan is turned off if the compressor is off. This happens with a delay of parameter 23.

* Defrost control possibilities.

The automatic defrost is started on a real-time (P60) clock basis and stops after the maximal defrost
time (P30), or earlier if the defrost sensor has reached the set defrost-end-temperature (P31). The

ALFANET  95

  has  a  number  of  automatic  defrost  possibilities  that  can  be  set  with  the  following

parameters;

Parameter 24 Type of defrost:

The 

ALFANET 95

 has three possibilities for defrosting; 

P24 = 0 At defrost only the relay FAN is switched on (natural defrosting).
P24 = 1 At defrost only the relay DEFR. is switched on (hot gas / electrical defrosting).
P24 = 2  At defrost the DEFR. and the FAN relays are both switched on (hot gas/elefan

defrosting).

Parameter 60 = 1 Defrosting on the  real-time clock

Here, the defrosting is started at fixed times (P61 up to and including P72).

* Adjusting the sensor.

The 

control sensor 

can be adjusted by means of the Offset control sensor parameter 05.

The 

defrost sensors

 can be adjusted by means of the Offset defrost sensor parameters 08 and 11.

For readout the temperature of the defrost sensors choose parameters 07 and 10.

Should a sensor of the 

ALFANET 95

 indicates 2

/

C too much, for example. Then the according Sensor

Offset must be lowered by 2

/

C.

* Operation of the Alarm.

When there is an error or an alarm, a error code message appears in the display. The 

ALFANET 95

remembers this error message, even if the problem has already been solved. 

The error message can be reset with the 

SET

 key. 

If, after pressing the 

SET

 key (=reset alarm) the alarm is not yet resolved, then the 

ALFANET 95

shows the temperature and error code alternately, if the alarm has been resolved then the error code
disappears and the temperature is shown again.