* Parameters ALFANET 85.

Para-
meter

Description

Range

Default 
Value

P 01
P 02
P 03

P 04
P 05

Switch differential cooling
Minimum set point setting
Maximum set point setting

Offset control sensor
Offset defrost sensor

0.1..15.0

C

-40.0..50.0

C

-40.0..50.0

C

-10.0..10.0

C

-10.0..10.0

C

0.5

-40.0

50.0

0.0
0.0

P 10
P 11
P 12

P 13
P 14

Switch on delay cooling
Switch off delay cooling
Parameter 10/11 in seconds or
 minutes
Minimum on time cooling
Minimum off time cooling

0..99
0..99
0 = sec 1 = min

0..99 minutes
0..99 minutes

0
0
0

0
0

P 20
P 21

P 22
P 23

P 24
P 25

P 26

Fan switch differential active
Switch differential fan

Fan off if cooling off
Switch off delay fan

Fan off during defrost
Switch on temperature fan after
 defrost
Switch on delay after defrost

0 = No 1 = Yes
0.1..50.0

C

0 = No 1 = Yes
0..99 minutes

0 = No 1 = Yes
-50.0..50.0

C

0..99 minutes

0

2.0

0
0

0

2.0

0

P 30
P 31
P 32

P 33
P 34
P 35

P 36

P 37
P 38

P 39

Defrost interval time
Maximum defrost time
End-of-defrost temperature

Cooling on during defrost
Defrost on compressor run time
Display fixed during defrost

Maximum display fixed time
 after defrost
Drip-off time
Start with defrost after power
 failure
Defrost delay after start-up

1..99 hours.
0..99 minutes
-40.0..50.0

C

0 = No 1 = Yes
0 = No 1 = Yes
0 = No 1 = Yes

0..99 minutes

0..99 minutes
0 = No 1 = Yes

0..99 minutes

12
15

2.0

0
0
0

10

0
0

0

P 40

P 41
P 42
P 43
P 44
P 45
P 46
P 47
P 48

Defrost on real time bases

Start defrost 1
Start defrost 2
Start defrost 3
Start defrost 4
Start defrost 5
Start defrost 6
Start defrost 7
Start defrost 8

0 = No 1 = Yes

00:00..23:59,OFF
00:00..23:59,OFF
00:00..23:59,OFF
00:00..23:59,OFF
00:00..23:59,OFF
00:00..23:59,OFF
00:00..23:59,OFF
00:00..23:59,OFF

0

00:00
04:00
08:00
12:00
16:00
20:00

OFF
OFF

P 50

P 51
P 52
P 53
P 54

P 55

P 56

Type alarm

Minimum alarm set point
Maximum alarm set point
Time delay minimum alarm
Time delay maximum alarm

Reset alarm when alarm
 disappears
Alarm relay off after manual
 reset of alarm

0 = none
1 = absolute
2 = relative
-40.0..50.0

C

-40.0..50.0

C

0..99 minutes
0..99 minutes

0 = No 1 = Yes

0 = No 1 = Yes

1

-40.0

50.0

0
0

0

0