background image

2

* Adjustment sensors.

The temperature sensor can be adjusted by using the Sensor Offset parameter 05.
Indicates the Sensor e.g. 2

C to much, the Sensor Offset has to be decreased with 2

C.

* Error messages.

In the display of the 

ALFA 71 MOD

 the following error messages can appear:

LO

- Minimum alarm.

Solution E1:

HI

- Maximum alarm.

- Check if the sensor is connected correctly.

E1

- Sensor-1 failure.

- Check sensor  (1000

 at 25

C).

- Replace sensor.

EEE

- Settings are lost.

Solution EEE:
- Reprogram the settings.

-L-

- In case of sensor short-circuit the display alternates between error-code 

E..

 and 

-L-

,

  as indication for a short-circuit sensor.

-H-

- In case of open-circuit sensor the display alternates between error-code 

E..

 and 

-H-

,

  as indication for  a open circuit sensor.

Reset Alarm.

When a error-messages appears it can be resetted by pushing the 

SET

 key.

The function of this key depends on parameter P37.

* Technical details.

Type

: ALFA 71 MOD Thermostat

Range

: -50/+50,0

C, above -10

C display per 0,1

C

Supply

: 12Vac 50/60Hz (-5/+10%)

Display

: 3-digit 7-segment display

Relays

: Ry1= Open 

SPST(NO)250V/8A (cos 

=1) of 250V/5A (cos 

=0.4)

  Ry2= Close 

SPST(NO)250V/8A (cos 

=1) of 250V/5A (cos 

=0.4)

  Ry3= Alarm

SPDT(NO/NC)250V/8A (cos 

=1) of 250V/5A (cos 

=0.4)

  Relays have one common (C).

Control

: By push buttons on front.

Front

: Polycarbonate IP65

Sensor

: SM 811/2m (PTC 1000

/25

C).

Analog output

: 0..10 Vdc PI output (cool or heat)

Dimensions

: 35 x 77 x 71,5mm (HWD)

Panel cutout

: 28 x 70mm (HW)

Accuracy

: ± 0,5% of the range.

- Provided with memory protection during power failure.
- Connections with screw terminals on the back side.
- Equipped with sensor failure detection.
- Special versions on request available.

Reviews: