Mechanical immersion thermostat 

DBAT is a series of clamp-on thermostats for use in cooling, heating 

and ventilation systems. 

Technical data

Sensor element   

Liquid-filled copper bulb

Contacts 

 

Dust-tight microswitches with SPDT  

 

 

 

 

contacts (heat/cool)

Breaking capacity   

15 (8) A, 24...250 V AC 

Ambient temperature 

-35…+65°C

Ambient humidity   

10…90 % RH (non-condensing)

Storage temperature 

-40…+70°C

Storage humidity   

< 95% RH

Housing  

  

Bayblend

®

 base, ABS cover

Weight   

 

410 g

Protection class   

IP65

Isolation class 

 

1

Article

Temperature 

range 

Max. temp. 

bulbo

Hidden 

setpoint

Hysteresis

DBAT-3

0…60 °C

75 °C

-

2…20 K

DBAT-3U

0…60 °C

75 °C

X

2…20 K

DBAT-5

20…90 °C

90 °C

-

2…20 K

DBAT-5U

20…90 °C

90 °C

X

2…20 K

Before installation or maintenance, the power supply must first be discon

-

nected in order to prevent potentially lethal electric shocks!  Installation or 

maintenance of this unit should only be carried out by skilled professio

-

nals.

Installation

The unit can be mounted in any position. 

Remove the external knob and unscrew both screws on the cover. Use 

the supplied screws when mounting on wall or other surface.  

Wiring

Heating:
Connect to the red and blue terminal. The contact will open when the 

temperature rises. 

Cooling:

Connect to the red and white terminal. The contact will open when the 
temperature drops. 

Hysteresis

Logic activation

Reset

The set range may be calibrated by carefully turning screw under the 

cover.

+

-

 

 

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low 

Voltage Directive (LVD) 2014/35/EU through product standards 
EN 60335-1.

RoHS

This product conforms to the Directive 2011/65/EU of the European 

 

Parliament and of the Council through standard EN 50581:2012. 

Contact

AB Industrietechnik srl  -  Via Julius Durst, 70
39042 BRESSANONE (BZ) Italy 
Tel.: +39 0472/830626

 [email protected], www.industrietechnik.it

REV

.A

 

JUL

 17  

EN

Red

Blue

White

ON

ON

OFF

OFF

Δ

NS

Δ

NS

Heating

Contacts red-blue

Cooling

Contacts red-white

ΔNS: Hysteresis
TSET: setting setpoint
ON: closed contact
OFF: open contact

regulation 2...20 K