8
11.03
Vedolux 37
Illustrations may differ from the actual product
Allowing for printing errors and errors on proofs
Electrical.connection
Supply
Fan
Circulation pump
YELLOW/GREEN
YELLOW/GREEN
BLUE
BLACK
BLACK
BLUE
15
16
17
20
22
21
25
26
27
28
0
1
2
3
4
5
6
0
0
0
0
0
0
psi
0
1
2
3
4
bar
c
F
0
2
1
1
4
8
6
0
0
2
0
0
0
0
0
1
1
4
4
8
2
2
2
6
0
0
0
0
0
0
0
RESET
ALARM
MAIN
SWITCH
FAN
START
FAN
STOP
Wiring.diagram.and.control.panel
15. Supply connection, 3-pole con-
nector.
a. cable part, socket.
b. chassis part, plug.
16. Fan connection,
5-pole connector.
a. cable part, plug.
b. chassis part, socket.
17. Connection for charging pump,
3-pole connector.
a. cable part, plug.
b. chassis part, socket.
18. Terminal block for internal earth
connections.
19. Start capacitor for fan motor.
20. Main switch.
21. Thermostat for fan and charging pump.
22. Fan start when the boiler is cold.
23. Relay.
BROWN
BLUE
YELLOW/GREEN
GREY
BLACK
SUPPLY
115 V~
FAN
CIRCULATION
PUMP
ALARM
25
15a
16a
17a
18
19
20
21
22
23
24
26
15b
17b
16b
Function
Start with the boiler cold.
Set the main switch, 20, to the ON-position – the green area must be
visible.
Set the thermostat, “FAN STO
P”, 21, to 120°C (250°F). The thermo-
stat detects the flue gas temperature.
Press “FAN START”, 22, the time relay, 24, is activat
ed and the fan
starts.
When the time set for the time relay, 30 minutes, is reached, the con-
tact changes, which means that the fan and the charging pump for
the accumulator system are controlled by the thermostat, 21.
When the firewood is burnt out and the flue gas temperature falls be-
low the value set for the thermostat, 21, the fan and charging pump
stop running.
If the boiler temperature exceeds 220°F, the overheating protection is
triggered. The fan stops running and the charging pump continues to
operate.
If the overheating protection, 25, is triggered, the “ALARM” indicator,
26, is lit. The relay, 23, prevents the time relay activating when the
overheating protection is triggered.
To reset the overheating protection, press “RESET”, 25, on the boiler
control panel. Note that it is not possible to reset the system until the
boiler temperature has dropped below 200°F.
24. Time relay, delayed cutoff.
25. Overheating protection.
26. Indicator showing triggered overheating
protection.
27. Thermometer, displays the boiler tem-
perature.
28. Pressure gauge showing the water pres-
sure in the heating system.
Electrical installation must be in accordance with the
applicable regulations, under the supervision of an
authorised installer.
Electrical.connection
The boiler is connected directly to the mains.
The electrical connections are at the rear of the boiler, in the form of
three quick connectors:
15. Mains connection, 115 V~, cable with quick connectors supplied.
16. Fan.
1�. Circulation pump, for charging the accumulator system.
Always disconnect the power supply to the
boiler before accessing the automation
cabinet or units powered by the boiler.