Installation

Function.of.accumulator.control

The accumulator control ensures that the boiler reaches a high 
working temperature before it starts charging the accumulator tank. 
It also prevents the return temperature to the boiler falling too low, 
helping to minimise the risk of condensation in the combustion 
chamber.
The charging pump of the accumulator system is controlled by a flue 
gas thermostat.

Expansion.system

The boiler is connected to a vented or unvented expansion system.
The volume of the expansion vessel is dimensioned according to 
the circumstances. The guideline values for volume are approx. 
5 % of the total system volume for vented systems, or 13- 15 % for 
unvented systems.

Vented   The distance between the top of the highest radiator and 

the expansion vessel must be

 at least 8.2 ft in order to pre-

vent oxygen saturation of the water in the heating system. 
The expansion vessel is connected in a continuous and 
unisolatable rise from the boiler’s expansion connection. 
To prevent damage occurring if the expansion system fails, 
for example because of freezing, the boiler should be fitted 
with a type approved safety valve, 21.8 psi.

Unvented  In unvented systems, the boiler must be fitted with a type 

approved safety valve, 21.8 psi, connected using an uniso-
latable pipe from the connection at the top of the boiler, as 
well as a bleed valve. 
The expansion vessel is best connected using ½” copper-
pipe, as shown in the diagram on the previous page.

The opening pressure of the safety valve is based on the 

lowest maximum pressure that any system component 

can withstand.

Cooling.coil.-.temperature.limiter

The boiler system must be equipped with a temperature limiter in 
accordance with the applicable regulations.
The boiler has a cooling coil which, combined with a suitable thermal 
valve, is used to prevent the boiler temperature exceeding 230°F if 
the water boils. Follow the instructions of the valve manu

facturer.

Turbulators

The five turbulators are installed in the flue gas pipes as shown in 
the diagram. The purpose of the turbulators is to introduce turbu-
lence to the flue gases, causing more heat to be transferred to the 
boiler water.
If the flue gas temperature falls too low (with a wide and long chim-
ney), there is a risk of condensation in the flue duct. To increase the 
temperature, the three upper turbulators can be removed, or cut to 
a length that produces a suitable flue gas temperature The draught 
hatch is another way of reducing condensation problems.

Bracket.for.cleaning.tool

The bracket for the cleaning tool can be fitted to either side of the 
boiler or any suitable place close to the boiler.

Draught.hatch

An extremely high chimney and/or strong winds can create a draught 
that is strong enough to allow combustion with the fan turned off. 
The solution is to install a draught hatch, which can reduce the 
draught to 0.04 - 0.06 in. water.

Pellet.burner/oil.burner

The Vedolux 3� is primarily designed to be fired by firewood, but can 
also be modified for pellets using a pellet burner. 
When the pellet burner is used, the accessories supplied with the 
pellet hatch set must be installed:
• Hatch, designed for the Viking Bio pellet burner.
•  Cover plate with draught hatch, instead of the fan on the rear of the 

boiler.

•  Cover plates for the primary damper behind the plate on the front 

of the boiler.

• Cover plate for the secondary damper.
It is possible to install an oil burner in the pellet hatch set. Fittings are 
available.
Because of the risk of condensation you should monitor the flue gas 
temperature. Check that the flue gas temperature is appropriate for 
the chimney type.
Otherwise, follow the instructions of the burner manufacturer.hatch.

x 3

x 2

30

31

30

31

Summary of Contents for Vedolux 37

Page 1: ...Installation operation and care Vedolux 37 2011 03 31 xxxxxx SMOKELESS...

Page 2: ...pansion system Overheating protection If there is a risk of freezing Draining the boiler Boiler cleaning Pellet oil burner Problems burning firewood 11 Component specification 12 Read this document ca...

Page 3: ...3 Vedolux 37 Illustrationsmaydifferfromtheactualproduct Allowingforprintingerrorsanderrorsonproofs To be completed when the Vedolux 37 is installed Serial number Installation date Installer Tel Other...

Page 4: ...Flue cleaning All flue ducts in the boiler are cleaned from the same hatch at the front of the boiler The hatch is hinged and is opened with a single op eration The flue ducts are round which means t...

Page 5: ...si 12 6 in2 Temperature design 220 F draught 0 04 in H2 O operating max 220 F Flue gas temperature 355 F Output wood moisture content 16 4 126 kBTU Voltage 115 V 60 Hz pellets 143 kBTU Current 0 3 A C...

Page 6: ...oiler is supplied with an angled flue pipe a flue pipe running up from the steel pipe is available as an accessory Fasten the flue pipe to the flange on the boiler using the 4 x M8 screws supplied wit...

Page 7: ...ce with the applicable regulations The boiler has a cooling coil which combined with a suitable thermal valve is used to prevent the boiler temperature exceeding 230 F if the water boils Follow the in...

Page 8: ...nges which means that the fan and the charging pump for the accumulator system are controlled by the thermostat 21 When the firewood is burnt out and the flue gas temperature falls be low the value se...

Page 9: ...have come out then wait a few weeks before trimming and splitting the wood During these weeks the leaves wilt and draw out the moisture After another few weeks of drying the wood has 25 30 moisture c...

Page 10: ...nt and the flue gas temperature has fallen to below 250 F the fan and charging pump to the accumula tor stop running 20 22 21 25 26 27 28 8 Bypass damper The boiler s bypass damper must only be used f...

Page 11: ...pipes be careful not to push the pipe cleaner through the grating damaging the fan Do not push the pipe cleaner further than the end of the pipe You can feel when you have reached the end from the di...

Page 12: ...system the static head If the difference is 16 4 ft the pressure is 7 3 psi if it is 32 8 ft the pressure is 14 5 psi The necessary pressure in the heating system depends on the height difference bet...

Page 13: ...icboilerisatitsmostefficientwhentheceramicishot The temperatureintheboilerthereforeneedstobeincreasedquicklybefore chargingbegins Theservicelifeoftheboilerisshortenedifthereisno controlsystem Addacont...

Page 14: ...m 1 4 30 00 30 Ceramic fibre paper 1x25mm m 2 34 3104 00 Grate front V 37 1 34 31 04 01 Grate rear V 37 1 9 32 00 07 Firewood hatch 1 10 32 00 18 Draught hatch V 37 1 37 00 60 Handle knob 25 mm 2 28 3...

Page 15: ......

Page 16: ...4644 226358 291 94 Kristianstad www varmebaronen se Sweden info varmebaronen se V rmebaronen AB retains the right to change the specification of included components without prior notice as part of it...

Reviews: