SERVICE
26
USE OF COILS
The heat pump can be equipped with a heating coil (15) 1m
2
heat surface or
with 2 heating coils (15) + (22) with a heating surface of 1.5 m
2
for the
bottom and 0.6 m
2
for the upper. By using supplementary heating from 2
systems for example solar and oil / gas boiler, the solar installations must be
connected to the lower and oil / gas boiler to the top. It is also possible to
connect both heating coils in series.
There must always be mounted thermostats on flow and container to ensure
the correct temperature. The water temperature must have 1st priority.
Heating of the heat pump through the heating coil the temperature in the
boiler may not exceed 65°C. At higher temperatures the heat pump's
refrigerant circuit can be damaged
Capacity of coils:
1 coil = 5.90 L
2 coils = Top: 3.83 L / Bottom: 9.57 L