Feature 05 – Output Delay:
To prevent rapid switching,
an output delay can be entered. This can be set from 00-15
minutes. The default is 00 which means there is no delay.
Feature 06 – Communication Address:
Non-functional on the
230V model.
Feature 07 – Temperature Up/Down Limit:
This function
allows you to limit the use of the up and down temperature
arrow keys. This limit is also applicable when the thermostat is
locked and so allows you to give others limited control over the
heating system.
Feature 08 – Sensor Selection
: On this thermostat, you can
select which sensor should be used. You can select between
air temperature only, floor temperature, or both. When you
enable both sensors, the floor sensor is used as a floor limiting
sensor and is designed to prevent the floor from overheating.
Note: Air Sensor only MUST NOT be used to control
underfloor heating. Floor Sensor or Both should be used.