Page 24
ECS-4+
FAN 2 RELATIVE SET POINT
The Fan 2 relative set point establishes the
temperature above the main set point at which
Fan 2 begins to operate at its minimum speed.
The value is a temperature
difference
from the
main set point.
The Fan 2 relative set point is adjusted in 0.5
degree increments from a minimum setting of
0.0°F (0.0°C) to a maximum setting of 18.0°F
(10.0°C).
Adjusting the relative set point of Fan 2:
•
rotate the Selector dial to position (4),
•
rotate the Adjustor dial counterclockwise to
decrease the relative set point, clockwise to
increase it.
The Fan 2 relative set point is displayed on the
front panel.
Example:
A main set point of 70°F along with a Fan 2 relative set
point of 5°F is selected. When room temperature
reaches 75°F, Fan 2 begins to operate at minimum
speed.
www.monitrol.com