FAN 2 MINIMUM SPEED
When the room temperature is at the Fan 2
relative set point, Fan 2 runs at minimum speed
set by this function. This value is entered as a
percentage of maximum speed. The Fan 2
minimum speed is adjusted in 2% increments
from a minimum setting of 12% to a maximum
setting of 100%.
Adjusting the minimum speed of Fan 2:
•
rotate the Selector dial to position (5),
•
rotate the Adjustor dial counterclockwise to
decrease fan speed, clockwise to increase
it.
The minimum fan speed is displayed on the
front panel.
CHAPTER 3 - USER’S GUIDE