Page 44
DIP-1/115
STATIC PRESSURE DISPLAY
This function displays the static pressure level
of the room when the automatic calibration is in
progress. Static pressure “Autocal” probe
required.
Static pressure is displayed in 0.01” H
2
O
increments from a minimum display of -0.20”
H
2
O to a maximum display of 0.20” H
2
O. If a
static pressure level lower than -0.20” H
2
O is
sensed,
LO
is displayed. On the other hand, if
a static pressure level higher than 0.20” H
2
O is
sensed,
HI
is displayed.
Displaying the static pressure level:
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode.
The static pressure level is displayed on the
DIP-1/115.
Note: When the automatic calibration is not in process,
the unit displays “F2”.
S.P.