Vaporless ARM-4073 Installation & Operation Manual Download Page 6

Vaporless Manufacturing, Inc. 

8700 East Long Mesa Drive, Prescott Valley, Arizona   86314 

800-367-0185     928-775-5191     Fax:  928-775-5309 

Email:  [email protected]    Web Site:  

www.vaporless.com

 

15.

 

Delay Timer Programming

 

 

Referring  to  Table  2,  select  the  volume  in  the  left-hand  column  which  first  exceeds  the 
measured bleed-back. The next four columns indicate the required switch settings. The right-
most column indicates the approximate time delay between pump cycles. 

16.

 The 

Time Delays

 shown in Table 2 are the minimum values needed to allow the leak detector 

to reset to its leak sense position. Longer delay times are acceptable, however, these longer 
delay times will increase the frequency of false alarms due to thermal contraction. 

17.

 

Pump Timer Programming

 

 

Referring  to  Table  1,  select  the  value  in  the  right-hand  column  (30  or  70  seconds)  which 
provides enough time for the turbine to repressurize the line from a zero pressure condition. 
The column to  the left indicates the required switch setting  for the selected operating time. 
Under normal conditions 30 second setting should be selected. If the line exhibits excessive 
bleed-back or extreme thermal contraction, then the 70 second setting may be selected. 

18.

 

Perform Leak Detector 3 GPH Test

 

 

This  completes  the  bleed-back  measurement  procedure  and  set-up  of  the  ARM  Repressure 
Module. A 3 GPH test should now be completed. 

LEAK DETECTOR TEST AT 3 GPH: 

Whether a new installation or the retrofit of an existing installation using VMI Leak Detectors, a 
leak  test  should  be  performed.  This  is  done  to  ensure  that  the  VMI  Leak  Detector  is  operating 
normally and that the selected ARM delay time is long enough for the VMI Leak Detector to return 
to its reset position. 

The following statements outline a procedure for testing the operation of the VMI Leak Detector. 
This procedure assumes the use of the Vaporless Model LDT-890 Leak Detector Tester to perform 
this task. 

The following procedure assumes no knowledge of the operation of the LDT-890 and therefore 
details each step of the process. The operation manual supplied with the LDT-890 provides ad-
ditional information and should be consulted by the technician. 

1.

 

Install LDT-890 Test Unit

 

 

If  the  LDT-890  has  not  been  installed,  follow  steps  1  through  11  in  the  procedure  outlined 
under Measuring System Bleed-Back. 

 

2.

 

Leak Calibration

 

 

With  the  large  beaker  (1000  ml)  under  the  LDT-890  discharge  hose,  set  the  selector  to  the 
C

ALIBRATE 

GPH position. Fuel will begin to flow into the beaker. 

3.

  The object of the next step is to calibrate the fuel flow from the test unit to the rate of 3 gallons 

per hour at 10 psi pressure at the discharge. This specification meets the requirements of the 
EPA regarding leak rate testing. 

Summary of Contents for ARM-4073

Page 1: ...Quality Petroleum Equipment Solutions for Over 30 Years ARM 4073 Automatic Repressure Module Installation Operation Manual Rev 05 08 2021 ...

Page 2: ...llowing statements outline the operation of the ARM 4073 1 With power applied the module is active and performs its timing functions The pump timer is the first to operate following the application of power Following the completion of the pump cycle the delay timer determines the elapsed time to the next pump cycle 2 There is a small switch module located in the center of the circuit board This mo...

Page 3: ...o difference whether the turbine s at your site are single phase or three phase The ARM 4073 only controls the coil on the turbine contactor just as any other authorization signal would The vast majority of installations for the ARM 4073 can be described with Figure 1 located on page 10 of this manual If you feel that your site is unique in some way please do not hesitate to consult with VMI for t...

Page 4: ...ith the lever positioned toward the terminal block power is applied to the module on position With the lever positioned away from the terminal block power is removed from the module off position Care should be exercised when operating the switch as voltage may be present on the L1 L2 terminals MEASURING SYSTEM BLEED BACK When under pressure all closed piping systems exhibit an elastic response tha...

Page 5: ...se set the selector to the DISPENSER NOZZLE position Purge the tester of air by allowing 800 to 1000 ml of fuel to flow into the beaker After purging the LDT 890 set the selector to the PRESSURE STEP TEST position 11 Purge the dispenser line by running several gallons of fuel into an approved safety container 12 Bleed Back Measurement Remove the dispenser authorization The turbine should stop runn...

Page 6: ... the bleed back measurement procedure and set up of the ARM Repressure Module A 3 GPH test should now be completed LEAK DETECTOR TEST AT 3 GPH Whether a new installation or the retrofit of an existing installation using VMI Leak Detectors a leak test should be performed This is done to ensure that the VMI Leak Detector is operating normally and that the selected ARM delay time is long enough for t...

Page 7: ...ZZLE position Fuel will begin to flow into the beaker After the reading on the right hand pressure gauge falls to zero set the selector to the PRESSURE STEP TEST position 8 Read Operating Pressure Authorize the dispenser The turbine will start running Watch for the turbine to achieve operating pressure as seen on the right hand pressure gauge Note this pressure reading and then remove the authoriz...

Page 8: ...Switch The turbine will start running Immediately return to the dispenser On the right hand pressure gauge of the LDT 890 verify that normal operating has been achieved Set the selector on the LDT 890 to the GPH TEST position This will introduce a 3 GPH leak to the system Because the leak detector has already stepped through to its fully open position nothing will change This leak must be introduc...

Page 9: ...3 Automatic Repressure Module is now fully functional and actively working to eliminate slow flow issues TIMER SWITCH SETTINGS Table 1 Pump Timer Switch Setting Switch Number Pump Time 1 OFF 30 seconds ON 70 seconds Table 2 Delay Timer Switch Settings Bleed Back ml Switch Number Delay Time minutes 2 3 4 5 150 OFF OFF OFF OFF 2 0 350 ON OFF OFF OFF 4 5 550 OFF ON OFF OFF 7 0 700 ON ON OFF OFF 9 5 9...

Page 10: ...om If you have any questions or concerns after reading this manual please contact VMI We are committed to customer service and the safety and satisfaction of our customers Manufactured by Vaporless Manufacturing Inc Electronics Division 8700 East Long Mesa Drive Prescott Valley Arizona 86314 Phone 928 775 5191 Website www vaporless com Technical Support electronics vaporless com ...

Reviews: