Vaporless ARM-4073 Installation & Operation Manual Download Page 3

Vaporless Manufacturing, Inc. 

8700 East Long Mesa Drive, Prescott Valley, Arizona   86314 

800-367-0185     928-775-5191     Fax:  928-775-5309 

Email:  [email protected]    Web Site:  

www.vaporless.com

 

ENCLOSURE & MOUNTING: 

The  module  is  designed  for  operation  in  a  non-hazardous,  indoor  environment  such  as  an 
equipment room. Holes are provided in the base for mounting the unit. Two holes are provided for 
the connection of ½” conduit fittings. A hole plug is provided for closing an un-used conduit hole. 

ELECTRICAL CONNECTIONS:

 

The best way to understand the operation of the ARM-4073 is to look at the device as though it 
were an additional dispenser being installed at the site. All dispensers typically have a 120 VAC 
power source being supplied to them. 

The ARM-4073 MUST be supplied with the same phase 

power as the dispenser(s).

 After determining the 120 VAC power source of the dispensers,  land 

the 120 VAC (hot) on terminal L1 of the ARM-4073 and the  (neutral) on terminal L2 of the ARM-
4073. Next, make a small jumper wire (minimum 16 AWG wire) that will land on terminals L1 
and K1. 

All dispensers have an authorization signal output that goes to some device that engages the turbine 
pump. In some instances, this signal may go directly to the A1 terminal on the pump contactor 
coil.  That  said,  look  at  terminal  K2  on  the  ARM-4073  as  though  it  were  another  authorization 
signal output from a dispenser and connect terminal K2 to where all the other authorization output 
signal wires terminate. It makes no difference whether the turbine(s) at your site are single phase 
or three phase. The ARM-4073 only controls the coil on the turbine contactor, just as any other 
authorization signal would. The vast majority of installations for the ARM-4073 can be described 
with Figure 1 located on page 10 of this manual. If you feel that your site is unique in some way, 
please do not hesitate to consult with VMI for technical support. 

1.

  Authorization signals are generally powered from a 120 VAC source. Because this signal is 

derived  from  one  of  the  phases  of  the  main  STP  power  source,  there  should  be  zero  volts 
between the signal side of the contactor’s coil when it is powered and one phase of the power 
mains. Using a voltmeter, determine which phase exhibits this condition. 

Though  unlikely,  please  note  that  the  source  of  the  authorization  control  signal  is  not  always 
apparent. It could be derived from a source that does not exhibit the characteristics noted in the 
previous paragraph.

  Note: It is the responsibility of the installer to determine the appropriate 

signal  (phase)  supplied  to  the  ARM-4073.  Selecting  the  incorrect  phase  will  likely  cause 
equipment damage and/or injury to the installer.

 

2.

  Connect terminal L1 on the ARM to 120 VAC dispenser power, and L2 terminal to neutral. 

3.

  Connect terminal  K2 on the ARM to the  authorization signal side of the contactor’s  coil or 

other device that relays a signal to the turbine pump contactor (i.e., DHI, ATG, etc.). 

4.

  Assuming you are powering the ARM-4073 with the same 120 VAC phase as the authorization 

signal, place a jumper wire between terminals L1 & K1 (16 AWG minimum wire size). Please 
see Figure 1 (wiring diagram) on page 10 of this document. 

 

 

Summary of Contents for ARM-4073

Page 1: ...Quality Petroleum Equipment Solutions for Over 30 Years ARM 4073 Automatic Repressure Module Installation Operation Manual Rev 05 08 2021 ...

Page 2: ...llowing statements outline the operation of the ARM 4073 1 With power applied the module is active and performs its timing functions The pump timer is the first to operate following the application of power Following the completion of the pump cycle the delay timer determines the elapsed time to the next pump cycle 2 There is a small switch module located in the center of the circuit board This mo...

Page 3: ...o difference whether the turbine s at your site are single phase or three phase The ARM 4073 only controls the coil on the turbine contactor just as any other authorization signal would The vast majority of installations for the ARM 4073 can be described with Figure 1 located on page 10 of this manual If you feel that your site is unique in some way please do not hesitate to consult with VMI for t...

Page 4: ...ith the lever positioned toward the terminal block power is applied to the module on position With the lever positioned away from the terminal block power is removed from the module off position Care should be exercised when operating the switch as voltage may be present on the L1 L2 terminals MEASURING SYSTEM BLEED BACK When under pressure all closed piping systems exhibit an elastic response tha...

Page 5: ...se set the selector to the DISPENSER NOZZLE position Purge the tester of air by allowing 800 to 1000 ml of fuel to flow into the beaker After purging the LDT 890 set the selector to the PRESSURE STEP TEST position 11 Purge the dispenser line by running several gallons of fuel into an approved safety container 12 Bleed Back Measurement Remove the dispenser authorization The turbine should stop runn...

Page 6: ... the bleed back measurement procedure and set up of the ARM Repressure Module A 3 GPH test should now be completed LEAK DETECTOR TEST AT 3 GPH Whether a new installation or the retrofit of an existing installation using VMI Leak Detectors a leak test should be performed This is done to ensure that the VMI Leak Detector is operating normally and that the selected ARM delay time is long enough for t...

Page 7: ...ZZLE position Fuel will begin to flow into the beaker After the reading on the right hand pressure gauge falls to zero set the selector to the PRESSURE STEP TEST position 8 Read Operating Pressure Authorize the dispenser The turbine will start running Watch for the turbine to achieve operating pressure as seen on the right hand pressure gauge Note this pressure reading and then remove the authoriz...

Page 8: ...Switch The turbine will start running Immediately return to the dispenser On the right hand pressure gauge of the LDT 890 verify that normal operating has been achieved Set the selector on the LDT 890 to the GPH TEST position This will introduce a 3 GPH leak to the system Because the leak detector has already stepped through to its fully open position nothing will change This leak must be introduc...

Page 9: ...3 Automatic Repressure Module is now fully functional and actively working to eliminate slow flow issues TIMER SWITCH SETTINGS Table 1 Pump Timer Switch Setting Switch Number Pump Time 1 OFF 30 seconds ON 70 seconds Table 2 Delay Timer Switch Settings Bleed Back ml Switch Number Delay Time minutes 2 3 4 5 150 OFF OFF OFF OFF 2 0 350 ON OFF OFF OFF 4 5 550 OFF ON OFF OFF 7 0 700 ON ON OFF OFF 9 5 9...

Page 10: ...om If you have any questions or concerns after reading this manual please contact VMI We are committed to customer service and the safety and satisfaction of our customers Manufactured by Vaporless Manufacturing Inc Electronics Division 8700 East Long Mesa Drive Prescott Valley Arizona 86314 Phone 928 775 5191 Website www vaporless com Technical Support electronics vaporless com ...

Reviews: