TSR-1 Remote Control
TruSine 4.5 kW Inverter
Page 15
Owner’s Manual
↑
XXX º C
↓
battery temperature sensor is installed
GENERAL INFORMATION Menu:
Press right control buttons to scroll up. Press left control buttons to scroll down.
50
↑
INVERTER SW
(
↓
)
(
↑
) REV. 1.13
↓
51
(
↑
)Model:
(
↓
)
(
↑
) TSC24-4500(D)
(
↓
)
52
(
↑
) TSR-2
(
↓
)
(
↑
) A88769-A
(
↓
)
53
(
↑
)VANNER POWER GRP(
↓
)
(
↑
)4282 REYNOLDS DR (
↓
)
54
(
↑
)HILLIARD, OHIO
(
↓
)
(
↑
)43026-1297, USA
(
↓
)
55
(
↑
)PH: 614-771-2718
(
↓
)
(
↑
)FAX: 614-771-4904
(
↓
)
56
(
↑
)http://
(
↓
)
(
↑
)www.vanner.com
(
↓
)
57
(
↑
)mail to:pwrsales
(
↓
)
(
↑
)@vanner.com
(
↓
)
ADVANCED CONTROL Menus:
60
Password
Use control buttons to enter password:
If correct go to
XXXX
upper left, lower right, lower left, upper right.
Step 61 if not
Go to Step 6
61
ADVANCED CONTROL Selects ADVANCED CONTROL submenu
Go to Step 70
62
COMMUNICATIONS
Selects the COMMUNICATIONS submenu
Go to Step 90
ADVANCED CONTROL Menu:
70
↑
InverterOutput
↓
Adjusts inverter AC output voltage setpoint
Go to Step 71
+ XXX VAC
-
and the ±10% range for Aux AC input voltage
71
↑
LowBatt Warn
↓
Adjusts inverter Low Battery Warning
Go to Step 72
+ XX.XX VDC
-
DC Volts setpoint
72
↑
LowBatt ShutDn
↓
Adjusts inverter Low Battery Shutdown
Go to Step 73
+ XX.XX VDC
-
DC Volts setpoint
73
↑
HighBat ShutDn
↓
Adjusts inverter High Battery Shutdown
Go to Step 74
+ XX.XX VDC
-
DC Volts setpoint
74
↑
BulkChrg Volts
↓
Adjusts Bulk Charge DC Volts setpoint
Go to Step 75
+ XX.XX VDC
-
75
↑
Bulk Chrg Amps
↓
Adjusts Bulk Charge DC Amps setpoint
Go to Step 76