background image

INCORPORATED

®

                                                                         Installation 

 

ITC-Series

 Inverter 

Page 23 

 

 

 

 

 

Owner‟s Manual 10/7/05 

with code.   Make  certain  to route the  Signal wires out of the provided port (lower most on the right 
side of the unit).   This is to insure that there are no problems that may arise from the poor insulation 
properties  of  most  signal  level  wire.    Make  certain  that  the  auxiliary  contact  and  option  wiring  are 
routed below the barrier, and the AC Power Wires above the barrier. 

Step 1:   Connect  the  AC  output.  Remove  the  front  cover  to  expose  the  AC  input  and  output  terminal  strips. 

Identify the right terminals labeled “AC Output”. Insert the output field wires through the nearest (to 
the board) strain relief into the AC wiring compartment. Tighten the strain relief. Connect the copper 
field wires to the proper AC output terminals and tighten to 9 lb-in max.  

Warning:

  Do  not  attempt  to  use  a  stranded  wire.    Stranded  wire  has  a  tendency  to break  off  some  of  the 

strands  and  will  drop  into  the  unit  causing  possible  failures.    If  a  stranded  wire  is  used,  the 
appropriate “ring terminal” must be used. 

Step 2:   Connect  AC  Input.  Iden

tify  the  terminal  strip‟s  terminals  labeled  “AC  Input”.  Insert  the  field  wires 

through the (closest to the front panel) strain relief into the AC wiring compartment. Tighten the strain 
relief.  Connect  the  copper  field  wires  to  the  proper  AC  input  terminals  and  tighten  to  9  lb-in  max. 
Replace the front cover. 

Warning:

  Do  not  attempt  to  use  a  stranded  wire.    Stranded  wire  has  a  tendency  to break  off  some  of  the 

strands  and  will  drop  into  the  inverter  causing  possible  failures.    If  a  stranded  wire  is  used,  the 
appropriate “ring terminal” must be used. 

Step 3:   Connect Bonding Lug. Use a 8 AWG or larger copper conductor to connect the chassis bonding lug 

to the chassis of the vehicle, the installation‟s grounding system, or to earth ground. 

Step 4:   Verify Installation. Verify all connections are tight and secure for maximum performance. 

System Start-up and Testing 

Step 1:  Completely  install  the  ITC-Series  Inverter/Charger  following  the  system  design  considerations  and 

instructions provided previously in this manual. 

Step 2:  Place the System Power On/Off switch located on the front of the inverter in the OFF position. 

Step 3:  Verify  that  the  external  GFCI  breaker  is  reset  and  connect  an  AC  load,  such  as  a  100-Watt  light. 

Note: some GFCI‟s require power to be applied before they will reset. 

Step 4:  Turn ON the battery DC power to the inverter. 

Step 5:  Turn ON the AC shore power (or generator) to supply the AC input power to the system 

Step 6:  Place the System On/Off Power switch located on the front of the inverter to the ON position. 

Step 7:  The Lights on the Control/Display Unit on the front of the inverter should come ON, by doing a lamp 

test. 

Step 8:  Disable  the  Charger  Operation  of  the  unit  by  pressing  the  Charger  ON/OFF  button  once  if  the 

Charger LIGHT is On or blinking.  This turns the charger function OFF. 

Step 9 

If the Inverter LIGHT is not On or blinking, enable the Inverter Operation of the unit by pressing the 

Inverter ON/OFF button once.  This turns the Inverter function ON. 

Step 10 The  AC  output  test  light  should  come  ON,  indicating  the  presence  of  shore  power  and  correct 

operation of the AC transfer switch. 

Step 11: 

Turn  off  the  AC  shore  power  input.  The  AC  output  test  light  should  immediately  quickly  blink 

once, indicating the transfer switch transferred the test light from shore power to inverter power.  

Step 12: 

At this point, apply AC loads up to rated output watts to verify full-power operation. 

Step 13: 

Apply  shore  power.  After  a  delay  the  AC  output  test  light  should  blink  and  the  ITC  Inverter 

LIGHT should blink indicating the transfer of the load from inverter power to shore power. 

Step 14: 

Test the battery charger operation  

Summary of Contents for ITC24-360

Page 1: ...anual 10 7 05 ITC Series Inverter Charger System Models ITC12 2100 and ITC12 3200 ITC24 3600 and SP00172 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 614 771 2718 1 800 ACPOWER www vann...

Page 2: ...INCORPORATED ITC Series ITC Series Inverter Page 2 10 07 05 Notes...

Page 3: ...CUSTOMER WIRING IDENTIFICATION 17 AC INPUT OUTPUT WIRING 18 DC BATTERY WIRING 18 FRONT PANEL CONTROL DISPLAY OUTLET 18 SYSTEM ON OFF SWITCH 19 REMOTE SIGNAL CONTACTS 19 INSTALLATION 19 BASIC GUIDELIN...

Page 4: ...7 Figure 1 4 6 Suspended Dimensions in Inches 11 F 8 Figure 1 4 7 Bottom Mount Dimensions in Inches 11 F 9 Figure 1 4 8 Control Display Unit Dimensions in Inches 11 F 10 Figure 1 4 9 Customer Terminat...

Page 5: ...he cover of this manual System Features and Specifications General Description The ITC Series system consists of a DC to AC true sine wave inverter a battery charger an automatic AC transfer switch an...

Page 6: ...shutdown of the Inverter at 10 5 21 0 VDC The SP00172 offers a Fan On contact instead of the Low Battery contact for turning on an external fan or blower when the ITC s fan is on Remote Power Switch...

Page 7: ...4 amps 3 amps No Load Inverter OFF 0 30 amps 0 30 amps Full power 208 amps 350 amps 195 amps INVERTER EFFICIENCY Nom 200 watts 77 77 500 watts 88 84 700 watts 88 87 1000 watts 88 89 1500 watts 86 89 2...

Page 8: ...IDE VIEW 11 12 15 16 OPTIONS CABLE ENTRY CHASSIS GROUND ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 DESCRIPTION BATTERY TERMINAL ACCESS REMOTE CABLE INPUT CONTROL DISPLAY PANEL INVERTER ON OFF SWITCH CHARGE...

Page 9: ...when enabled but not on 2 Inverter On Off Button Enables Disables Inverter Function 3 Charger Indicator Light Solid when on flashes when enabled but not on 4 Charger On Off Button Enables Disables Cha...

Page 10: ...allowing access to user AC and control terminals through a removable front cover ACCESS PANEL REMOVABLE FROM FRONT WHEN UNDER TABLE MOUNTED DOCKED DISPLAY CONTROL PANEL DC TERMINATIONS POWER ON OFF S...

Page 11: ...10 7 05 18 10 7 8 19 1 4 13 5 8 16 3 4 8 1 8 7 5 16 8 3 4 ITC DIMENSIONS FOR SUSPENDED MOUNTING F 7 Figure 1 4 6 Suspended Dimensions in Inches 19 1 4 18 10 7 8 16 3 4 13 5 8 7 5 16 8 ITC DIMENSIONS F...

Page 12: ...HOT NEU GND AC INPUT P15 HOT NEU GND AC OUTPUT P6 P5 REMOTE MASTER AND SLAVE CONNECTORS REMOTE SWITCH REMOTE LED COM N O N O LOW BATT FAN ON COM GENSTART P3 BATTERY TEMP SENSOR P7 F 10 Figure 1 4 9 C...

Page 13: ...Battery Shutdown 10 5 21 0 VDC setpoint the inverter will shut OFF Auto restart will restart the inverter after battery voltage rises above the Low Battery Warning 11 0 22 0 VDC setpoint after 5 minu...

Page 14: ...rge Stage and begins the Absorption Charge Stage The charger will not enter the Bulk Stage again until shore power is re applied or until the charger or the system is turned ON again VOLTAGE CURRENT T...

Page 15: ...harging by preventing the charging stages from reaching their trigger points or may cause the battery to run down even though the charger is ON T 1 Figure 2 2 2 Battery Charger Factory Setpoints Guide...

Page 16: ...r Terminations and likewise a similar set of Normally Open Contacts are available to indicate a Low Battery or Fan On condition Caution The battery charging process will be affected if 12 24 VDC loads...

Page 17: ...6 7 8 9 10 11 12 DIPSWITCH FUNCTION SWPOSITION OFF ON OFF ON OFF ON SLAVE MASTER Note After a new switch setting is set the power switch must be cycled on the main unit for the new setting to take eff...

Page 18: ...d P15 NOTE The AC output voltage and the required AC input voltage of the ITC is 120 VAC 60Hz DC Battery Wiring A DC wiring compartment is located behind the wiring panel on the right side of the unit...

Page 19: ...l to the circuit INSTALLATION Unpacking the Inverter Inspect the shipping container and equipment for loose or damaged parts If any damage is found immediately notify the freight carrier Basic Guideli...

Page 20: ...ons do not use the vehicle chassis as the DC negative conductor Use a cable the same size as the DC positive to go directly from the inverter to the battery negative 4 Route the AC and DC power wiring...

Page 21: ...rough separate strain reliefs located at the right front of the unit WARNING Never make electrical connections live Make the connections to the inverter first and the battery last Make certain the ON...

Page 22: ...on lug style that will accept up to 10 AWG copper wire Model ITC12 3200 The 26 7 amp at 120 volt 3200 watt inverter output capability requires 10 AWG wire minimum is used for the AC output The AC tran...

Page 23: ...installation s grounding system or to earth ground Step 4 Verify Installation Verify all connections are tight and secure for maximum performance System Start up and Testing Step 1 Completely install...

Page 24: ...power This power can be used to operate various AC driven appliances Typical DC power sources include batteries that store electrical energy power generated from a vehicle alternator or renewable ener...

Page 25: ...ly equal to watts and are obtained by multiplying volts times current produced or used by a device To properly determine an inverter size in watts for your application decide which AC loads you plan t...

Page 26: ...recharge cycling that is typical of most inverter installations These batteries are available in the maintenance free style where the electrolyte does not need to be checked or replenished and they a...

Page 27: ...gine The 24 volts is usually provided by connecting two 12 volt batteries in series and sometimes by connecting four 6 volt batteries in series The ratings of the series connected battery bank remain...

Page 28: ...rting the engine and operating the inverter This is a common practice in a service vehicle where the engine runs all the time and allows the alternator to provide continuous charging for the battery I...

Page 29: ...ing for lead acid batteries and 50 of the battery s C for gel cell batteries The C rate is numerically equal to the amp hour capacity for the battery For example a 280 amp hour battery has a C rate of...

Page 30: ...corrosion free 2 Check air ventilation openings for dust and other obstructions 3 Examine receptacle indicators and switches for cracks and breaks in insulation material Trouble Shooting The Unit doe...

Page 31: ...Page 31 Owner s Manual 10 7 05 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 1 800 AC POWER 1 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail pwrsales vanner com Ma...

Reviews: