background image

19

106918

OWNER’S MANUAL

INSTALLATION

Continued

 WARNING: Improper installa-

tion, adjustment, alteration, ser-
vice, or maintenance can cause
injury or property damage. Refer
to this manual. For assistance or
additional information, consult a
qualified installer, service
agency, or gas supplier.

BURNER REMOVAL

 CAUTION: Before proceed-

ing, make sure the entire unit is
cool.

1.

Remove the top and bottom louvers and
screen. Open the glass door (left or right
side).

2.

Carefully remove the log set.

3.

Remove the screw that attaches the
burner to the bracket.

4.

Slide the burner towards the front of
the unit, lift, and remove from the fire-
box.

5.

To reinstall the burner, slide the burner
towards the rear of the unit and secure
burner to bracket with screw.

 CAUTION: Make certain the

orifice is inside the venturi tube's
air shutter, see Figure 48.

6.

Replace the log set, close door with
latches, and attach screen and louvers.

DECORATIVE FACING

Any noncombustible material may be used
for facing (glass, tile, brick, etc.) as long as
the proper clearances are observed (see
Clearances, page 4). 

IMPORTANT:

 Lou-

vered openings must not be obstructed, and
upper and lower panels must remain remov-
able for servicing. Use only heat-resistant,
noncombustible mortar or adhesive when
securing facing material.

Note:

 Combustible material, such as wood,

that has been fireproofed is not considered
noncombustible.

Left

Right

Bac

k

F

ront

Left

F

ront

Right

Bac

k

B

B

A

A

Figure 44 - Installing Logs “A” (Top View)

Figure 45 - Installing Logs “B ” (Top View)

PILOT ASSEMBLY
ADJUSTMENT

The pilot assembly is factory preset for the
proper flame height. Alteration to these set-
tings may have occurred during shipping and
handling. If this is the case, some minor
adjustment may be necessary and should be
done by a qualified technician. To access the
pilot assembly, the glass door must be opened.
The proper settings for the thermopile height
should be at a distance of 3/8" to 1/2" from the
pilot flame as shown in Figure 47.

BURNER FLAME
ADJUSTMENT

Figure 47 - Correct Pilot Flame Pattern

The air shutter, located at the underside of the
main burner (see Figure 48), has been factory
preset to the proper air-to-gas ratio which
results in an even, clean burning flame across
the burner (see Figure 49). If readjustment is
necessary, you can restore the proper air-to-
gas ratio by loosening the air shutter screw
and rotating the air shutter until the proper
flame setting is achieved (the shutter's nor-
mal setting is “full opened”. Do not forget to
retighten the air shutter screws.

Figure 49 - Burner Flame Patterns

CORRECT

INCORRECT
CLOSE
SHUTTER

INCORRECT
OPEN
SHUTTER

Short, Sharp,
Blowing Flame

Long, Blue Flame
with Yellow Tips

Long, Uneven,
Yellow Flame

1/8"

(3mm)

3/8" - 1/2"
(9.5mm-12.3mm)

Figure 48 - Connecting Venturi and Orifice

Air Shutter

Orifice

Burner

Firebox Bottom

Venturi
Tube

Burner Gas Line

Left

Right

Bac

k

F

ront

D

C

C

D

E

Figure 46 - Installing Twigs “C, D, E ” (Top
View)

Summary of Contents for VDDVF36STN/STP

Page 1: ...s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier SAVE THIS BOOK This...

Page 2: ...ensions Back of Surround Back of Surround Figure 2 VDDVF36STN STP See Thru Dimensions Left Side Surround Right Side Surround Rating Plate Location Left Side Surround Right Side Surround GLOSSARY OF TE...

Page 3: ...ing other than the type of gas approved for use in this gas appliance NOTICE Check local building codes for area requirements be fore installing this appliance This appliance when installed must be el...

Page 4: ...N Do not block re quired air spaces with insula tion or any other material Do not obstruct the effective opening of the appliance with any type of facing material MANTEL CLEARANCES Woodwork such as wo...

Page 5: ...maxi mum thickness of 3 4 Do not recess venting terminals into a wall or siding Install horizontal venting with a 1 4 rise for every 12 of run toward the ter mination You may paint the vent terminal...

Page 6: ...bove paved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minimu...

Page 7: ...to select the proper length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired Th...

Page 8: ...ows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations These lugs will slide...

Page 9: ...utside edge of the vent cap Position the vent cap in the center of the 7 1 2 or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is...

Page 10: ...Vertical V and Horizontal H maxi mums and minimums The same amounts apply for flexible venting FGFVK Vent Kit Shown Horizontal Termination Configurations Figures 21 through 23 show different con figur...

Page 11: ...90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 4 max 6 min 8 max 7 min 10 max 8 min 15 max 20 max 20 max Figure 23 Horizontal Termination Configuration for Rigid Venting Using Two 90 Elbows w...

Page 12: ...ances air space to combustibles when passing through ceilings walls roofs enclo sures attic rafters etc Do not pack air spaces with insulation Also note maxi mum vertical rise of the venting sys tem a...

Page 13: ...ort box vertically and horizontally using a level Temporarily tack the support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the supportbox from the top corne...

Page 14: ...figuration With No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 20...

Page 15: ...12 Firestop Support Roof Flashing RTV Silicone Vertical Termination and 26 screws D1000 7 x 12 Galvanized Coaxial Pipe 6 pcs D1010 7 x 24 Galvanized Coaxial Pipe 6 pcs D1020 7 x 48 Galvanized Coaxial...

Page 16: ...t be properly connected to a standard 120 VAC power source Refer to Wiring Diagram on page 23 An outlet box with two receptacles has been supplied for your convenience located on the lower left side o...

Page 17: ...ible gas line pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its indi vidual manual shut off valve during any pressure testing of...

Page 18: ...service technicians installing gas to the appliance CAUTION Do not connect appliance before pressure test ing gas piping Damage to the gas valve may result and an un safe condition may be caused O F F...

Page 19: ...roofed is not considered noncombustible Left Right Back Front Left Front Right Back B B A A Figure 44 Installing Logs A Top View Figure45 InstallingLogs B TopView PILOT ASSEMBLY ADJUSTMENT The pilot a...

Page 20: ...se proper safety gloves to re move the broken glass door Dis card safely A glass door kit can be ordered through your local distributor Do not substitute other material for the glass WARNING Children...

Page 21: ...der water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been un der water LIGHTING INSTRUCTIONS 1...

Page 22: ...s on the hand held remote control unit for up to 3 sec onds to assure proper operation GHRC Operation 2a Press ON OFF button to turn the burners on and off When turning burners off the pilot will rema...

Page 23: ...ilot will not stay lit burner will produce flames and soot fireplace will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is bad If so contact your local propane LP gas supplier WIRI...

Page 24: ...o light the fireplace 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your gas supplier 5 Refer to section on pilot lighting 6 Have a qualified technician replace...

Page 25: ...6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut i...

Page 26: ...burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Clean burner or replace burner orifice 1 Adjust the log set so that the flame does not excessively impin...

Page 27: ...ent cap installation 1 Gas leak See Warning statement above 2 Control valve defective 1 Gas leak See Warning statement above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame...

Page 28: ...ural 105883 01 25701 Propane LP 105883 02 25702 If in need of replacing have a qualified technician replace it WALL SWITCH KIT 105742 01 22180 Wall Switch 105902 01 14112 Cover Plate 105903 01 14113 W...

Page 29: ...01 25854 Left Right Bottom 105887 01 25856 Rear 106924 01 27374 Front 105888 01 25885 BURNER ASSEMBLY 105885 01 27243 REPLACEMENT PARTS Continued Front Bottom Left Right Bottom Front Used for See Thru...

Page 30: ...____________________________________________ _______________________________________________________________________________________________ ___________________________________________________________...

Page 31: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 32: ...l be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIE...

Reviews: