Operating Procedures
EZCT™
and
EZCT-
10
41
6.11 Diagnostic
The EZCT diagnostic mode allows the user to view the EZCT excitation voltage (Vx), excitation
current (Ix) outputs and the H input voltage (Vh) simultaneously on the display. This feature
allows the user to trouble shoot a connection problem to a CT or to verify the EZCT excitation
voltage and current readings against external meters.
The EZCT will turn off the excitation output voltage after 1 minute while in this mode.
NOTE
Both pairs of X1 and X2 cables must be connected to the excitation voltage (Vx), and the H1 &
H2 cables must be connected to sense the Vh voltage in order for this mode to work properly.
Table 18 EZCT Diagnostic Procedures
STEP
ACTION
EZCT
DISPLAY
18-1
From the main menu, press key #3
(DIAGNOSTIC)
18-2
Pr
e
s
s
t
he
“
ENTER”
ke
y
18-3
Turn the Voltage Control knob to raise the Vx
voltage.
18-4
Pr
e
s
s
t
he
“
STOP”
ke
y
t
o
e
xi
t
t
he
Di
a
gnos
t
i
c
Mode.
CAUTION! CABLE WILL
BE ENERGIZED!
“ENTER”
TO
CONTI
NUE
DIAGNOSTIC
Vx=0.0
Ix=0.0000
Vh=0.0 00
“STOP”
TO
EXI
T
DIAGNOSTIC
Vx=100.0
Ix=0.0050
Vh=0.0100
“STOP”
TO
EXI
T
1.RUN TEST
07/06/06
2.SETUP
16:27:00
3.DIAGNOSTIC