CT-6500 Operating Instructions
43
9.11 Set-Up Open Analysis Points
Table 16.0 Setting Up "OPEN" Analysis Points Using Distance
STEP
OPERATION
ACTION
DISPLAY
1
SELECT SET UP MENU.
PRESS # 3 KEY.
1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2
SELECT ANALYSIS POINT.
PRESS # 1 KEY.
1. OPEN TIMING
2. CLOSE TIMING
3. PRINT SETTING
4. TEST PLAN
3
SELECT OPEN TIMING.
PRESS # 1 KEY.
OPEN ANALYSIS PT 1
1. PERCENT OF STROKE
2. DISTANCE FROM CLOSE
3. CONTACT #1
4
SELECT DISTANCE FROM CLOSE.
PRESS # 2 KEY.
OPEN ANALYSIS PT 1
DISTANCE FROM CLOSE
VALUE: XX.XX in
"ENTER" TO CONFIRM
5
ENTER 1 INCH.
PRESS KEYS 0-9 TO
SET 1.00. USE THE
“ENTER” KEY TO
CONFIRM.
OPEN ANALYSIS PT 1
DISTANCE FROM CLOSE
VALUE: 01.00 in
"ENTER" TO CONFIRM
6
CONFIRM ENTRY.
PRESS THE "ENTER"
KEY.
OPEN ANALYSIS PT 2
1. PERCENTAGE OF STROKE
2. DISTANCE FROM CLOSE
3.C/- TIME
7
SELECT DISTANCE FROM CLOSE.
PRESS # 2 KEY.
OPEN ANALYSIS PT 2
DISTANCE FROM CLOSE
VALUE: XX.XX in
"ENTER" TO CONFIRM
8
ENTER 2 INCHES.
PRESS KEYS 0-9 TO
SET 2.00 INCHES.
OPEN ANALYSIS PT 2
DISTANCE FROM CLOSE
VALUE: 02.00 in
"ENTER" TO CONFIRM
9
RETURN TO MAIN MENU.
PRESS THE "ENTER"
KEY.
1.TIME BRKR
2.GET RSLT
3.SET UP
4.DIAGNOSTICS