CT-6500 Operating Instructions
45
9.12 English/Metric or Rotary Transducer Selection
The CT-6500 supports and displays both English and Metric calculations from the breaker's
travel parameters such as the stroke, velocity and other parameters. The user can switch from
one system to the other by following the steps in Table 17.0. Rotary transducer requires the user to
enter the defined linear distance in millimeters or inches, per one degree of rotary motion as seen
in Table 17.1.
Table 17.0 Select Metric Units of Measure
STEP
OPERATION
ACTION
DISPLAY
1
SELECT SET UP MENU.
PRESS # 3 KEY.
1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2
SELECT MEASUREMENT UNITS.
PRESS # 2 KEY.
SELECT UNITS
1. ENGLISH
2. METRIC
3. ROTARY TRANSDUCER
3
SELECT METRIC.
PRESS # 2 KEY.
1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC
Table 17.1 Select Rotary Transducer
STEP
OPERATION
ACTION
DISPLAY
1
SELECT SET UP MENU.
PRESS # 3 KEY.
1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2
SELECT MEASUREMENT UNITS.
PRESS # 2 KEY.
SELECT UNITS
1. ENGLISH
2. METRIC
3. ROTARY TRANSDUCER
3
SELECT ROTARY TRANSDUCER.
PRESS # 3 KEY.
ROTARY ENCODER:
1. ENGLISH (In./deg)
2. METRIC (MM/deg)
4
SELECT INCH PER DEGREE.
PRESS #1 KEY.
INCHES/DEGREE
0.014 in/deg
5
ENTER 0.50 INCH PER DEGREE.
ENTER 0.50 USING 0-
9 KEYS.
INCHES/DEGREE
0.500 in/deg
6
RETURN TO MAIN MENU.
PRESS THE “ENTER”
KEY.
1. TIME BRKR
2. GET RSLT
3. SET UP
4. DIAGNOSTIC